2015-06-20 07:56:49 | PLAN REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS INCLUDING |
| INSTALLATION INSTRUCTION DRAWINGS FOR THE SINGLE HUNG |
| WINDOWS THAT WERE INSTALLED ( FL14604 ACCORDING TO THE |
| PHOTOS) AS REQUIRED BY DCA RULE 9N-3. CIRCLE THE |
| APPROPRIATE INSTALLATION TYPE ON THE PRODUCT APPROVAL. |
| |
| 2) SUBMIT PRODUCT APPROVALS, KEY PLANS AND INSTALLATION |
| SCHEDULE FOR IMPACT PROTECTION DEVICES, IF THE WINDOWS |
| ARE NOT LARGE MISSLE IMPACT RATED. FBC EXISTING |
| BUILDING 606.4 & DCA RULE 9N-3 |
| |
| 3) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN |
| LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16. THE |
| WIND LOAD DOCUMENT FROM HARVEY KOEHNEN, PE HAS A |
| FACSIMILE SIGNATURE. THE ENGINEER IS REQUIRED TO SIGN |
| BY HAND THE LICENSEE'S HANDWRITTEN SIGNATURE. FAC |
| 61G15-23.002 |
| |
| 4) SHOW THE INTERIOR WALLS AND DESIGNATE THE ROOMS ON |
| THE WINDOW LOCATION FLOOR PLAN. THIS IS REQUIRED TO |
| DETERMINE THAT THE BEDROOM EGRESS REQUIREMENTS ARE IN |
| COMPLIANCE. |
| SECTION 604 MEANS OF EGRESS |
| 604.1 GENERAL. |
| MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION |
| SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 601.1 AND |
| THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE. |
| EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL |
| DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5 PERCENT |
| REDUCTION IN THE CLEAR OPENING DIMENSIONS OF |
| REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED. |
| |
| 5) SUBMIT TWO SETS OF PLANS THAT SHOW THE EXISTING |
| CABINET LAYOUT AND THE PROPOSED CABINET LAYOUT. IF |
| ADDITIONAL COUNTER SPACE IS ADDED, THEN ADDITIONAL |
| ELECTRICAL RECEPTACLES MAY BE REQUIRED. FBC 107.2.1 |
| |
| 6) SUBMIT TWO SETS OF PLANS THAT SPECIFY THE LOCATIONS |
| AND EXTENT OF THE PROPOSED DRYWALL REPAIRS. FBC 107.2.1 |
| |
| 7) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| |
| 8) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 9) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE |
| VALUATION FOR THIS PROJECT ON THE PERMIT APPLICATION OF |
| $3500.00 IS LOW. |
| |
| 10) FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| 10 FEET OF EACH SLEEPING ROOM. |
| |
| 11) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| ADDRESSED. |
| |
| 12) RE-SUBMITTAL PROCEDURE |
| YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE |
| SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER |
| DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED |
| APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE |
| REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN |
| CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK |
| WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER. |
| ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED |
| SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH |
| THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED |
| SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED |
| FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS, |
| RESUBMIT THOSE SHEETS. |
| IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO |
| (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS |
| SHALL BE SUBMITTED. |
| |
| |
| |
| |
| |