Plan Review Notes
Plan Review Notes For Permit 15030428
Permit Number 15030428
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-30 07:51:20PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTION
 DRAWINGS FOR THE LARGE MISSILE IMPACT RATED SINGLE HUNG
 WINDOWS ( FL17377 ) AS REQUIRED BY DCA RULE 9N-3.
 CIRCLE THE APPROPRIATE INSTALLATION TYPE ON THE PRODUCT
 APPROVAL. ( THROUGH FRAME OR FIN )
  
 2) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED IS FOR
 OPENING PROTECTIVE DEVICES, SUCH AS, STORM PANELS. THE
 ANCHOR SPACING OF 8" O.C. IS NOT ACCEPTABLE FOR THE
 THROUGH FRAME INSTALLATION FOR WOOD. THE MAXIMUM
 SPACING IS 5" O.C. CENTER PER THE PRODUCT APPROVAL. FBC
 301.1
  
 3) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN
 LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 4) SHOW THE INTERIOR WALLS AND DESIGNATE THE ROOMS ON
 THE WINDOW LOCATION FLOOR PLAN. THIS IS REQUIRED TO
 DETERMINE THAT THE BEDROOM EGRESS REQUIREMENTS ARE IN
 COMPLIANCE.
 SECTION 604 MEANS OF EGRESS
 604.1 GENERAL.
 MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 601.1 AND
 THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE.
 EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL
 DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5 PERCENT
 REDUCTION IN THE CLEAR OPENING DIMENSIONS OF
 REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED.
  
 5) SUBMIT TWO SETS OF PLANS THAT SHOW THE EXISTING
 CABINET LAYOUT AND THE PROPOSED CABINET LAYOUT. IF
 ADDITIONAL COUNTER SPACE IS ADDED, THEN ADDITIONAL
 ELECTRICAL RECEPTACLES MAY BE REQUIRED. FBC 107.2.1
  
 6) SUBMIT TWO SETS OF PLANS THAT SPECIFY THE LOCATIONS
 AND EXTENT OF THE PROPOSED DRYWALL REPAIRS. FBC 107.2.1
  
 7) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 8) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 9) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE
 VALUATION FOR THIS PROJECT ON THE PERMIT APPLICATION OF
 $3500.00 IS LOW.
  
 10) FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
 12) RE-SUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  
  
  
  
  
  
  
  