Date |
Text |
2015-03-17 07:53:02 | |
| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15030405 |
| ADD: 4801 DREHER TRL N. |
| CONT: HEDRICK BROTHERS |
| TEL: (561)689-8880 |
| E-MAIL:[email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. MARCH 18/ 2015 |
| ACTION: DENIED |
| |
| IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| 1) SHEET A-1 THE EARLY LEARNING GALLERY SHOWS AN |
| OCCUPANT LOAD OF 16. 773 SQ. FT./ 16= 45.8 SQ. FT. PER |
| OCCUPANT. PLEASE PROVIDE HOW THIS CALCULATION WAS |
| FIGURED. THE PLANS ARE FOR THE SCIENCE MUSEUM WHICH WE |
| WOULD USE 15 SQ. FT. PER OCCUPANT FOR VIEWING AREAS |
| WHERE THE PUBLIC WILL GATHER. |
| 2010 FBC-B TABLE 1004.1.1. WHEN 773 SQ. FT. /15= 52 |
| OCCUPANTS (FBC-B TABLE 1004.1.1.) THIS WILL REQUIRE (2) |
| EXITS (TABLE 1015.1) AND 1/3RD THE DISTANCE APART FBC-B |
| 1015.2.1 EXCEP # 2. |
| |
| PLEASE PROVIDE WHAT THE USAGE OF THIS ROOM WILL BE AND |
| WHY THE REDUCED OCCUPANT LOAD ONLY REQUIRING 1 EXIT |
| FROM THIS AREA. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| |
| |