Plan Review Notes
Plan Review Notes For Permit 15030357
Permit Number 15030357
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-20 15:51:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ON THE INSTALLATION SCHEDULE, SPAN IS THE DISTANCE
 FROM ANCHOR TO ANCHOR. SEE, FOR EXAMPLE, OPENING 11.
 VERTICAL INSTALLATION, SPAN FOR A 60" OPENING WILL
 EXCEED 3'.
  
 2. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHARTS. IN THIS CASE, BASED ON THE
 MARKS ON THE PRODUCT APPROVAL, IT APPEARS THAT THE
 CONNECTION TYPES PROPOSED ARE C4 / C1. IF A VERTICAL
 INSTALLATION IS PROPOSED AS STATED, AND SPAN EXCEEDS
 5', 12" ANCHOR SPACING IS NOT ADEQUATE FOR C4
 CONNECTION.
  
 FBC 2010 RESIDENTIAL 301.
  