1 |
|
Notes |
Date |
Text |
2015-04-09 17:55:54 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE WIND LOAD PROGRAM DOCUMENTS ARE BARELY LEGIBLE | | AND NOT CLEAR ENOUGH TO BE USED FOR PUBLIC RECORD. FBC | | 107.2.1.4 | | | | 2) THE PLANS INDICATE THAT THE STRUCTURE IS LOCATED IN | | EXPOSURE C AND THE WIND LOAD DOCUMENTS THAT WERE | | SUBMITTED ARE DIFFICULT TO SEE BUT APPEAR TO SPECIFY | | EXPOSURE B. THE COMPONENT PRESSURES FOR THE DOORS | | APPEAR TO BE FOR A STRUCTURE WITH A MEAN ROOF HEIGHT | | LESS THAN 15 FEET LOCATED IN EXPOSURE D WITH A 170 MPH | | VULT WIND SPEED. FBC 107.2.1 & FBC-R 301.2.1.4 | | | | 3) THE WIND LOAD SUBMITTAL DOCUMENTS WHICH ARE SIGNED | | BY THE P.E. (DANIEL MOSS) ARE REQUIRED TO BE SEALED. FS | | 471 AND FAC 61G-15. | 2015-03-11 15:23:43 | COORDINATE WITH ART LANGE. STOP WORK ORDER ISSUED. |
|