2015-04-25 10:34:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030326
 ADD: 5335 N. MILITARY TRL. SUITE # 33
 CONT: MIKE MOORE CONSTRUCTION
 TEL: (561)301-9468
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISO:
 AT RATED WALLS PLEASE HAVE THE FIRE STOPPING
 MANUFACTURER SPEC SHEET IN COMPLIANCE WITH:
 2010FBC-B 713.3.1.2 THROUGH-PENETRATION FIRESTOP
 SYSTEM. THROUGH PENETRATIONS SHALL BE
 PROTECTED BY AN APPROVED PENETRATION FIRESTOP SYSTEM
 INSTALLED AS TESTED IN ACCORDANCE
 WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE
  
 WALL PENETRATED.