Plan Review Notes For Permit 15030314 |
Permit Number |
15030314 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-11 06:09:07 | 1) SHT. P-1 NOTES A TOTAL BTU LOAD OF 1,039,000 BUT MY | | CALCULATIONS COME TO 1,264,00 INCLUDING THE EXISTING | | GENERATOR. TABLE 402.4 (20) SHOWS THE MAXIMUM BTU LOAD | | ON 3/4" PE PIPE AT 2 PSI AT 200 FT. IS 736,000 ( THERE | | IS NO ROW FOR 185 FT.). THE SIZE OF THE PE LINE FROM | | THE POINT OF CONNECTION AT THE METER UP TO THE TEE FOR | | THE GAS RANGE SHALL BE 1" ( THE 60 FT. SECTION) | | 2) THE 1/2" GALVANIZED DROP TO THE RANGE SHALL BE 3/4" | | PER TABLE 402.4 (2) OF 2010 FUEL GAS CODE. THE MAXIMUM | | BTU LOAD ON 1/2" SCH. 40 PIPE @ 60 FT. IS 65,000 BTU'S. | | 3) SIZE THE LINE FROM THE POOL HEATER REGULATOR TO THE | | NEW POOL HEATER. IF IT IS SCH. 40 METAL IT SHALL BE 1" | | PER TABLE 402.4 (2) OF THE FUEL GAS CODE. | | 4) SHOW THE LINE SIZES AND PIPE MATERIAL FROM THE | | MEDIUM PRESSURE REGULATORS TO THE APPLIANCES WHERE | | NEEDED. | | 5) NOTE # 12 ON SHT. P-1 NOTES THAT PE PIPE WILL BE | | INSTALLED OUTSIDE UNDERGROUND ONLY BUT THE PLAN CLEARLY | | SHOWS THE PIPE GOING UNDER THE SLAB TO THE NEW GAS | | GRILL. CLARIFY. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|