2015-04-08 16:19:38PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK ON THE PRIMARY PERMIT APPLICATION
 STATES ADD A/C. HOWEVER NO MECHANICAL PLANS OR PERMIT
 APPLICATION WAS SUBMITTED. FBC 107.1
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 3) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT (SCHEDULE ON PLANS) AND LOCATION
 AND DUCT SYSTEMS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15.