Plan Review Notes For Permit 15030245 |
Permit Number |
15030245 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-07-01 04:35:01 | 1 ) SHT. 4 OF 6 & SHEET 6 OF 6 SHOWS A WATER | | DISPENSER.THIS IS NOT ACCEPTABLE AS COMPLIANT WITH 2010 | | FPC TABLE 403.1. A DRINKING FOUNTAIN IS REQUIRED FOR | | THIS OCCUPANCY AND FOOTNOTE "E" AT THE BOTTOM OF TABLE | | 403.1 STATES THAT THE MINIMUM NUMBER OF REQUIRED | | DRINKING FOUNTAINS SHALL COMPLY WITH TABLE 403.1 AND | | THE FLORIDA BUILDING CODE, ACCESSIBILITY. SECTION 211.2 | | OF THE FAC REQUIRES A MINIMUM OF 2 DRINKING FOUNTAINS. | | DELETE THE WATER DISPENSER FROM THESE SHEETS. | | 2) THE PLAN THAT WAS SUBMITTED FOR THE NEW DRINKING | | FOUNTAINS HAS A COPY OF AN ENGINEER'S SIGNATURE AND | | SEAL. THE PLAN SHALL BE SIGNED AND SEALED BY THE | | ENGINEER AND SHALL COMPLY WITH FL. ADMIN. CODE RULE | | 61G15-23.002. | | 3) THE NEW SHEET FOR THE DRINKING FOUNTAINS SHALL BE | | INSERTED INTO EACH SET OF PLANS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|