2015-07-01 04:35:011 ) SHT. 4 OF 6 & SHEET 6 OF 6 SHOWS A WATER
 DISPENSER.THIS IS NOT ACCEPTABLE AS COMPLIANT WITH 2010
 FPC TABLE 403.1. A DRINKING FOUNTAIN IS REQUIRED FOR
 THIS OCCUPANCY AND FOOTNOTE "E" AT THE BOTTOM OF TABLE
 403.1 STATES THAT THE MINIMUM NUMBER OF REQUIRED
 DRINKING FOUNTAINS SHALL COMPLY WITH TABLE 403.1 AND
 THE FLORIDA BUILDING CODE, ACCESSIBILITY. SECTION 211.2
 OF THE FAC REQUIRES A MINIMUM OF 2 DRINKING FOUNTAINS.
 DELETE THE WATER DISPENSER FROM THESE SHEETS.
 2) THE PLAN THAT WAS SUBMITTED FOR THE NEW DRINKING
 FOUNTAINS HAS A COPY OF AN ENGINEER'S SIGNATURE AND
 SEAL. THE PLAN SHALL BE SIGNED AND SEALED BY THE
 ENGINEER AND SHALL COMPLY WITH FL. ADMIN. CODE RULE
 61G15-23.002.
 3) THE NEW SHEET FOR THE DRINKING FOUNTAINS SHALL BE
 INSERTED INTO EACH SET OF PLANS.
  