Plan Review Notes
Plan Review Notes For Permit 15030245
Permit Number 15030245
Review Stop P
Sequence Number 1
Notes
Date Text
2015-03-31 08:55:431) SHT. A-1 - THE CLEARANCE AROUND THE WATER CLEARANCE
 SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES MINIMUM(59 INCHES IF FLOOR
 MOUNTED WATER CLOSET) MEASURED PERPENDICULAR FROM THE
 REAR WALL PER SEC. 604.3.1 OF THE 2010 FL. ACCESS.
 CODE. AS DESIGNED, THE RESTROOM IS NOT WIDE ENOUGH.
 MINIMUM WIDTH SHALL BE 85 INCHES.
 2) SHT. A-2 - THE GRAB BARS SHALL BE LOCATED A MINIMUM
 OF 33 INCHES AND 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE PER
 2010 FAC SEC.609.4.
 3) THE SEAT HEIGHT OF THE WATER CLOSET SHALL COMPLY
 WITH FAC SEC.604.4. SHOW THE HEIGHT ON THE PLAN.
 4) THE LOCATION OF THE WATER CLOSET SHALL COMPLY WITH
 THE 2010 FAC SEC.604.2.
 5) TOILET PAPER DISPENSER SHALL COMPLY WITH FAC SEC.
 604.7.
 6) MINIMUM KNEE AND TOE CLEARANCES SHALL BE PROVIDED
 UNDER THE LAVATORY PER THE 2010 FAC SEC.306.2 & 306.3.
 7) SHT. P-1, NOTE # 5 REFERS TO A SHOWER YET NO SHOWER
 IS SHOWN ON THE PLANS. CLARIFY.
 8) SHT. A-1 - THE TOILET ROOM SHOWS A CABINET ON THE
 BACKSIDE DOOR WHICH WOULD INTERFERE WITH THE DOOR
 OPENING. CLARIFY.
 9) THE DEMO PLAN LINES AND HARD TO SEE FOR THE OBJECTS
 TO BE REMOVED. CLEARLY SHOW THE DEMO DETAILS ON THE
 PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  