2015-03-14 10:22:27 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15030245 |
| ADD: 1215 TAMARIND AVE |
| CONT: BRINMAR CONSTRUCTION |
| TEL: ( 904)360-9066 |
| E-MAIL:[email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| 1ST REVIEW |
| DATE: SAT. MARCH 14/ 2015 |
| ACTION: DENIED |
| |
| 1) THE VALUE OF THE WORK INDICATED IN THE PERMIT |
| ($7,500.00) VALUE IS EXTRMELY, LOW. IF NOT BROUGHT UP |
| TO THE FAIR MARKET VALUE PLEASE SEE HOW A CALCULATED |
| VALUE WILL BE OBTAINED. |
| PERMIT FEES/ PLAN REVIEW: |
| W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) THE PLANS SHOW (2) NEW OPENINGS THROUGH THE EXTERIOR |
| WALL AND THERE ARE NO STRUCTURAL PLANS SUBMITTED BY THE |
| FL LICENSED P. E. GEORGE ROUMAIN. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: T; ALL FENESTRATION PENETRATIONS, EXTERIOR |
| DOORWAYS AND ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR |
| ELEVATIONS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| SITE PLAN W/ PROPERTY LINES AND OR SURVEY PROVIDE |
| DIMENSIONS FROM THE PROPERTY LINES IT APPEARS THER MAY |
| BE PROPERT LINES WITH 5 FT OF EXTERIOR WALLS. |
| PARKING & ACCESSIBLE PARKING WITH AN ACCESSIBLE ROUTE |
| TO THE ENTRANCE. |
| OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| TABLE 503, TABLE 602 & TABLE 705.7) |
| FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE SPRINKLERED OR NOT |
| OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| USAGE OF ROOMS, OR ROOM IDENTIFICATION NUMBERS |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| DOORS |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| WIND REQUIREMENTS |
| BUILDING ENVELOPE |
| ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| SITE REQUIREMENTS |
| ACCESSIBLE ROUTE |
| VERTICAL ACCESSIBILITY |
| TOILET AND BATHING FACILITIES |
| DRINKING FOUNTAINS |
| |
| 3) THE SUBMITTED PRODUCT APPROVAL NOA : 13-1021.05 |
| ALDORA MK-2 ALUMINUM ENTRANCE DOOR W/ WO TRANSOM NO |
| ELEVATION TO SHOW IF THIS IS A SINGLE DOOR, DOUBLE WITH |
| OR WITH OUT TRANSOM. NONE OF THE SIZE OF THE UNIT, TYPE |
| OF GLAZING, TYPE OF ANCHORS AND ASSOCIATED PRESSURES |
| ARE PROVIDED. THE PLANS DO NOT INDICATE IF THIS SAME |
| UNIT IS TO BE INSTALLED AT THE FRONT ENTRY AND OR AT |
| THE 2 NEW OPENINGS THAT ARE BEING CREATED. |
| COMPONENTS & CLADDING |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 5) THE WIND DESIGN CRITERIA IS NOT PROVIDE, SHOW |
| COMPLIANCE WITH : |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| |
| 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| NEGATIVE TABLE 1609.2(2) |
| |
| 6) SHEET A1 DETAIL # 2 SHOWS AN EXISTING WOOD RAMP AND |
| DETAIL OF A NEW RAILING. SHEET A1 THE CUT SECTION DOES |
| NOT SHOW ANY TOP LANDING REQUIED BY THE CODE. SEE FBC-B |
| 1010.6 AND FL ACCESS. CODE . LANDINGS SHALL COMPLY WITH |
| SECTIONS FBC-B 1010.6.1 THROUGH 1010.6.5. |
| |
| 7) SHEET A-1 THE DOOR AT THE TOP OF THE RAMP DOES NOT |
| COMPLY WITH THE 2010 FBC ACCESS. 404.2.4.1 MANEUVERING |
| CLEARANCES. |
| |
| 8) SHEET A-1 DOES NOT SHOW WHAT THE ROOM IS RIGHT |
| BEHIND THE PROPOSED NEW ACCESSIBLE RESTROOM. THE OTHER |
| ISSUE IS HOW WILL THE DOOR OPEN WHEN THE PLANS SHOW A |
| CABINET BLOCKING THE DOOR SWING. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIED, A DISCREPANCY IN THE PLANS. |
| PLEASE MAKE CORRECTIONS. |
| |
| 9) SHEET A-1 DETAIL 3/ A4 SHOWS A NEW HANDRAIL SYSTEM, |
| PLEASE SEE TTHE REQUIREMENTS FOR EXTENSIONS 2010 |
| FBC-ACCESS. CODE 505.10. |
| |
| 10) THE ELEVATED AREA OFTHE BUILDING PLEASE SHOW |
| COMPLIANCE WITH 2010 FL ACCESS. CODE 201.1.1 VERTICAL |
| ACCESSIBILITY. |
| |
| 11) SHEET A-4 THE CONCRETE RAMP AND HANDRAIL GAURD RAIL |
| LOCATION IS NOT SHOWN ON SHEET A1, NOT ABLE TO COMMENT |
| ON THIS BECAUSE OF TO MANY VARIABLES WITHOUT THE |
| LOCATION PROVIDED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED, LOCATION. |
| |
| 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: (561) 805-6715 |
| FAX: (561)805-6676 |
| E-MAIL: [email protected] |