Date |
Text |
2015-03-30 10:28:15 | ****PROVISO**** |
| ****ISSUED AT CONTRACTOR'S RISK**** |
| ****REVISION REQUIRED PRIOR FINAL INSPECTION**** |
| ****ITEM #8 REQUIRED PRIOR TO FIRST INSPECTION**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| PLANS WERE NOT REVISED - SAME PLANS SUBMITTED |
| COMMENTS FROM PREVIOUS LIST: |
| |
| 1. OK |
| |
| 2. FOOTINGS TO BE 12" BELOW UNDISTURBED GRADE, FBC |
| 1809.4. |
| |
| 3. OK |
| |
| 4. FBC 3105.1.1.1, SHOW DISTANCE TO THE BOTTOM OF THE |
| AWNING STRUCTURE. |
| |
| 2ND REVIEW - THIS WAS WRITTEN ONTO THE PLAN AS 7'8", |
| AND ONLY ONE HAND REVISED SET WAS PROVIDED. ENGINEER IS |
| TO INCORPORATE THIS CHANGE INTO HIS DRAWING. |
| INDIVIDUALS OTHER THAN THE ENGINEER CANNOT REVISE THE |
| ENGINEER'S PLAN; ENGINEER'S PLAN IS TO PROVIDE ENOUGH |
| INFORMATION TO DEMONSTRATE CODE COMPLIANCE. |
| |
| 5. GAZEBO FOUNDATION, PROVIDE A STRUCTURAL DETAIL FBC |
| 107. THE PLAN INDICATES THAT THIS IS "BY OTHERS." |
| |
| 2ND REVIEW, FOUNDATION PLAN FOR THE GAZEBO WAS NOT |
| SUBMITTED, SO THERE IS NOTHING FOR EITHER REVIEW OR |
| INSPECTION. THIS PORTION IS EXCLUDED FROM THIS PERMIT |
| UNTIL A PLAN IS MADE AVAILABLE. |
| |
| 6. FBC 2010 ACCESSIBILITY FAIR HOUSING SECTION 3, ITEM |
| C(1) REQUIRES THAT "THE PUBLIC AND COMMON USE AREAS ARE |
| READILY ACCESSIBLE AND USABLE BY THE HANDICAPPED |
| PERSONS". THE GAZEBO IS GRAPHICALLY SHOWN 6" ABOVE |
| GRADE. PROVIDE A DETAIL FOR ACCESSIBLE ENTRY. |
| |
| 2ND REVIEW, NOT ADDRESSED. CONTRACTOR STATED THAT A |
| RAMP WILL BE BUILT, AND AN EMAIL BETWEEN TWO |
| INDIVIDUALS MAKING REFERENCE TO A RAMP WAS PROVIDED |
| (RELATIONSHIP TO JOB UNCLEAR; NEITHER WAS THE |
| CONTRACTOR OR THE ENGINEER). REVISION IS TO INCLUDE |
| ACCESSIBLE ROUTE TO THE GAZEBO AS WELL AS GAZEBO |
| FOUNDATION. |
| |
| 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| THE GAZEBO SHINGLES, FAC9N-3. |
| |
| 2ND REVIEW, A FLORIDA STATE PRODUCT APPROVAL COVER |
| SHEET WAS PROVIDED. THIS APPROVAL INCLUDES NINE |
| DIFFERENT PRODUCTS; SPECIFIC PRODUCT PROPOSED NOT |
| INDICATED AND THE EVALUATION REPORT/INSTALLATION |
| INSTRUCTIONS WERE NOT PROVIDED. WITH EITHER THE |
| REVISION OR THE ROOF PERMIT, PROVIDE A COMPLETE PRODUCT |
| APPROVAL. THIS SHOULD BE REVIEWED BY EOR PRIOR TO |
| SUBMITTAL, FBC 107.3.4. |
| |
| 8. ADJUST VALUE TO INCLUDE ALL PROPOSED IMPROVEMENTS. |
| PROVIDE A COPY OF THE CONTRACT(S), FBC 109. |
| |
| 2ND REVIEW, NOT ADDRESSED. VALUE IS TO INCLUDE THE |
| VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT, |
| ENGINEERING - EVERYTHING EXCEPT FOR THE VALUE OF LAND. |
| PROVIDE A COPY OF THE CONTRACT(S) FOR THIS JOB. |
| |
| 9. PROVIDE SLOPE AND CROSS SLOPE FOR SIDEWALKS, FBC |
| 2010 ACCESSIBILITY FAIR HOUSING SECTION 3 (ACCESSIBLE |
| ROUTE). |
| |
| 2ND REVIEW, NOT ADDRESSED. THIS PERMIT IS ISSUED AT |
| CONTRACTOR'S RISK. |
| |
| NEW COMMENTS: |
| |
| A. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW |
| COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE |
| INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS. |
| THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL. |
| |
| B. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT |
| FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER |
| (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO |
| HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT |
| WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE |
| LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT |
| BE NOTARIZED. |
| |
| C. THE PLANS FOR THE GAZEBO AND PERGOLA ARE |
| PHOTOCOPIES. DOCUMENTS PREPARED BY AN ENGINEER AND |
| SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, |
| DATED ORIGINALS FS471. SUBMIT ORIGINALS WITH THE |
| REVISION. |
| |