2015-03-05 10:50:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| SHEET A-1, THERE IS INCORRECT REFERENCE TO FIRE CODES - |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2009 EDITION. |
| |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2010 EDITION. |
| |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| |
| SHEET A-1 REFERNECES THAT THE BUILDING IS SPRINKLERS - |
| THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE |
| FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND |
| COMPLIANCE. |
| |
| PLEASE INDICATE ON THE PLANS THAT THE LIFE SAFETY |
| SYSTEMS, FIRE ALARM AND/OR FIRE SPRINKLER SHALL REMAIN |
| ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| SHEET E-1, P-1 INDICATES A PIECE OF EQUIPMENT IN THE |
| KITCHEN AREA MARK WITH A RED LETTER "F". WHAT IS THIS |
| PIECE OF EQUIRPMENT? WHAT ADDITONAL PIECES OF EQUIPMENT |
| PROPOSED FOR THE KITCHEN? WHAT IS THE PROPOSED COOKING |
| IN THIS KITCHEN? COOKING MEETING THE PROTECTION |
| REQUIREMENTS CONTAINED WITHIN NFPA 96 SHALL COMPLY WITH |
| THAT CODE.. |
| |
| SHEET A-2 DOES NOT INDICATE ANY EXIT SIGNS WITHIN THE |
| KITCHEN AREA. THIS AREA HAS ACCESS TO 2 EXITS. ONE |
| ADDITIONAL EXIT SIGN SHALL BE ADDED TO THE KITCHEN AREA |
| AT THE AREA OF THE CORRIDOR. |
| |
| SHEET A-2 INDICATES THE ADDITION OF A NEW WALL |
| SEPARATING THE KITCHEN AND THE WAREHOUSE. PLEASE |
| PROVIDE THE REQUIRED FIRE RATING OF THIS WALL AND THE |
| DOOR. |
| |