2015-03-03 07:25:06 | BUILDING PLAN REVIEW |
| PERMIT: 15030033 |
| ADD: 1300 FLORIDA MANGO RD BAY # 17 |
| CONT: COMPLETE SOLUTIONS |
| TEL: (561)337-7793 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| 1ST REVIEW |
| DATE: TUES. MARCH 03/2015 |
| ACTION: DENIED |
| |
| 1A) PLANS INDICATE 4 PAGES, ONLY (3) SUBMITTED. |
| |
| 1B) SHEET A2, 2OF 4. DISCREPANCY IN PLANS AND PERMIT |
| APPLICATION. THE PERMIT APPLICATION INDICATES WORK IS |
| TO BE COMPLETED IN BAY # 17. THE PLANS SHOW ONE WALL |
| BEING REMOVED IN BAY # 17 AND THE MAJORITY OF THE WORK |
| BEING COMPLETED IN BAY 18. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED FOR THE |
| LOCATION OF WORK TO BE COMPLETED UNDER THIS PERMIT. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. L. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION... |
| |
| 2) SHEET A2, 2OF 4. IN BAY # 18 WHERE THE MAJORITY |
| OFTHE WORK IS SHOWN THERE IS A BAY WITH 2 LARGE GARAGE |
| DOORS THAT SEPERATE THE OFFICE AREA FROM THE WAREHOUSE |
| AREA. THE DESIGNER OF RECORD INDICATES THIS WALL TO BE |
| A 1 HOUR FIRE RATED WALL WITH WALL SECTION DETAIL. NOTE |
| THE DOORS LOCATED IN THIS WALL DO NOT INDICATE THERE |
| FIRE RATING NOR CLASSIFICATION. PLEASE SEE 2010 FBC-B |
| TABLE 715.4. |
| |
| 3) SHEET A2, 2OF 4. IN BAY # 18 WHERE THE NEW OFFICES |
| ARE BEING BUILT AS WELL AS THE LARGER STORAGE AREA TO |
| THE LEFT OF THE OFFICE, THE DESIGN OF RECORD HAS NOT |
| DECLARED A OCCUPANCY. |
| 2010 FBC-B 302.1 GENERAL. |
| STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE |
| CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF |
| THE GROUPS LISTED BELOW. A ROOM OR SPACE THAT IS |
| INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR |
| DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE |
| REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE |
| PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED. |
| STRUCTURES WITH MULTIPLE OCCUPANCIES OR USES SHALL |
| COMPLY WITH SECTION 508 MIXED OCCUPANCIES.SEE TABLE |
| 508.4. THE WAREHOUSE WALL ADJOINING THE KITCHEN DOES |
| NOT SHOW ANY FIRE RATING? |
| |
| 4) SHEET A2, 2OF 4. THE PLANS INDICATE A KITCHEN, THERE |
| IS NO SINK, RANGE/ STOVE OR HOOD IF THIS AREA IS TO BE |
| CONSIDERED A KITCHEN. 2010 FBC-B F] 903.2.11.5 |
| COMMERCIAL COOKING OPERATIONS. AN AUTOMATIC SPRINKLER |
| SYSTEM SHALL BE INSTALLED IN COMMERCIAL KITCHEN EXHAUST |
| HOOD AND DUCT SYSTEM WHERE AN AUTOMATIC SPRINKLER |
| SYSTEM IS USED TO COMPLY WITH SECTION 904. |
| |
| 5) SHEET A2, 2OF 4. IN THE NEW OFFICES THERE IS GLAZING |
| NEXT TO THE OFFICE DOORS, SHOW COMPLIANCE WITH 2010 |
| FBC-B 406.4 HAZARDOUS LOCATIONS. |
| THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS |
| LOCATIONS REQUIRING SAFETY GLAZING MATERIALS: |
| 6. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL |
| ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF |
| THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER |
| VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND |
| WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS |
| THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE. |
| |
| 6) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1203.1 |
| BUILDINGS SHALL BE PROVIDED WITH NATURAL VENTILATION IN |
| ACCORDANCE WITH SECTION 1203.4, OR MECHANICAL |
| VENTILATION IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE, MECHANICAL. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |