Plan Review Notes
Plan Review Notes For Permit 15030033
Permit Number 15030033
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-03 07:25:06BUILDING PLAN REVIEW
 PERMIT: 15030033
 ADD: 1300 FLORIDA MANGO RD BAY # 17
 CONT: COMPLETE SOLUTIONS
 TEL: (561)337-7793
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: TUES. MARCH 03/2015
 ACTION: DENIED
  
 1A) PLANS INDICATE 4 PAGES, ONLY (3) SUBMITTED.
  
 1B) SHEET A2, 2OF 4. DISCREPANCY IN PLANS AND PERMIT
 APPLICATION. THE PERMIT APPLICATION INDICATES WORK IS
 TO BE COMPLETED IN BAY # 17. THE PLANS SHOW ONE WALL
 BEING REMOVED IN BAY # 17 AND THE MAJORITY OF THE WORK
 BEING COMPLETED IN BAY 18.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED FOR THE
 LOCATION OF WORK TO BE COMPLETED UNDER THIS PERMIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. L.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION...
  
 2) SHEET A2, 2OF 4. IN BAY # 18 WHERE THE MAJORITY
 OFTHE WORK IS SHOWN THERE IS A BAY WITH 2 LARGE GARAGE
 DOORS THAT SEPERATE THE OFFICE AREA FROM THE WAREHOUSE
 AREA. THE DESIGNER OF RECORD INDICATES THIS WALL TO BE
 A 1 HOUR FIRE RATED WALL WITH WALL SECTION DETAIL. NOTE
 THE DOORS LOCATED IN THIS WALL DO NOT INDICATE THERE
 FIRE RATING NOR CLASSIFICATION. PLEASE SEE 2010 FBC-B
 TABLE 715.4.
  
 3) SHEET A2, 2OF 4. IN BAY # 18 WHERE THE NEW OFFICES
 ARE BEING BUILT AS WELL AS THE LARGER STORAGE AREA TO
 THE LEFT OF THE OFFICE, THE DESIGN OF RECORD HAS NOT
 DECLARED A OCCUPANCY.
 2010 FBC-B 302.1 GENERAL.
 STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED BELOW. A ROOM OR SPACE THAT IS
 INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
 STRUCTURES WITH MULTIPLE OCCUPANCIES OR USES SHALL
 COMPLY WITH SECTION 508 MIXED OCCUPANCIES.SEE TABLE
 508.4. THE WAREHOUSE WALL ADJOINING THE KITCHEN DOES
 NOT SHOW ANY FIRE RATING?
  
 4) SHEET A2, 2OF 4. THE PLANS INDICATE A KITCHEN, THERE
 IS NO SINK, RANGE/ STOVE OR HOOD IF THIS AREA IS TO BE
 CONSIDERED A KITCHEN. 2010 FBC-B F] 903.2.11.5
 COMMERCIAL COOKING OPERATIONS. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE INSTALLED IN COMMERCIAL KITCHEN EXHAUST
 HOOD AND DUCT SYSTEM WHERE AN AUTOMATIC SPRINKLER
 SYSTEM IS USED TO COMPLY WITH SECTION 904.
  
 5) SHEET A2, 2OF 4. IN THE NEW OFFICES THERE IS GLAZING
 NEXT TO THE OFFICE DOORS, SHOW COMPLIANCE WITH 2010
 FBC-B 406.4 HAZARDOUS LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS:
 6. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL
 ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF
 THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER
 VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND
 WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS
 THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE.
  
 6) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1203.1
 BUILDINGS SHALL BE PROVIDED WITH NATURAL VENTILATION IN
 ACCORDANCE WITH SECTION 1203.4, OR MECHANICAL
 VENTILATION IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
  
  
  
  
  