Plan Review Notes For Permit 15030015 |
Permit Number |
15030015 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-01 18:34:05 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE ENGINEERING FOR PROPOSED SIGN, FBC 1609. | | ENGINEERING SHOULD INCLUDE A STRUCTURAL DETAIL FOR THE | | SIGN (SIZE OF MATERIAL, CABINET CONSTRUCTION). | | | | 2ND REVIEW, STRUCTURAL DETAIL FOR SIGN (SIZE OF | | MATERIAL, CABINET CONSTRUCTION) NOT PROVIDED. GAUGE OF | | ALUMINUM, THICKNESS OF PLEXIGLASS, PLEXIGLASS CHANNEL | | SPEC, ETC. IT IS NOT CLEAR HOW ENGINEER CAN STATE THAT | | THIS SIGN WILL WITHSTAND THE WIND LOADS WITH NO | | INFORMATION. | | | | TWO DIFFERENT WIND CRITERIA ARE GIVEN. PICK ONE; IS | | THIS 160MPH CAT 1 OR 180MPH EXPOSURE C? IF IT'S 160MPH, | | WHAT IS THE EXPOSURE CLASSIFICATION? | | | | PROVIDE CALCULATIONS FOR THE FOUR FASTENERS SPECIFIED | | FOR THE 18" X 8' CABINET SIGN. | | | | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | 109. | | | | 2ND REVIEW, NOT ADDRESSED. | | | | A SET HAS BEEN RETAINED. | | | | |
|