Plan Review Notes For Permit 15020941 |
Permit Number |
15020941 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-07-17 07:31:48 | 2ND REVIEW: FBC 2010 MECHANICAL | | PERMIT #15020941 | | 7/17/15. | | | | NOTE: I HAVE RE-PRINTED THE COMMENTS FROM THE PREVIOUS | | (1ST) REVIEW BELOW. THE PLANS WERE RE-SUBMITTED WITHOUT | | THE REQUESTED CORRECTIONS. | | | | 1ST REVIEW: FBC 2010 MECHANICAL | | 6/26/15 | | | | 1) THE MECHANICAL CLOSET LOUVERED DOOR #2 SHALL BE OF | | NON-COMBUSTIBLE MATERIALS: THE DOOR SCHEDULE IS | | INDICATING A WOOD DOOR- REFERENCE SECTIONS 202, 602, | | AND 603.1 FBC-10 MECHANICAL. | | 2) INDICATE HOW THE O/A DAMPER IS BEING CONTROLLED- | | REFER TO SECTION 503.2.5.4 FBC-10 ENERGY CONSERVATION. | | 3) THE TOILET EXHAUST FAN FOR BATH-1 SHALL HAVE A | | MINIMUM EXHAUST CAPACITY OF 100 CFM'S PER TABLE 403.3 | | FOOTNOTE E. 50 CFM PER TOILET OR URINAL. | | 4) PROVIDE TIE DOWN ENGINEERING FOR THE AC CONDENSERS- | | SECTION 301.12 FBC-10 MECHANICAL | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|