Plan Review Notes For Permit 15020941 |
Permit Number |
15020941 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-06-26 14:57:53 | 1ST REVIEW: FBC 2010 MECHANICAL | | 6/26/15 | | | | 1) THE MECHANICAL CLOSET LOUVERED DOOR #2 SHALL BE OF | | NON-COMBUSTIBLE MATERIALS: THE DOOR SCHEDULE IS | | INDICATING A WOOD DOOR- REFERENCE SECTIONS 202, 602, | | AND 603.1 FBC-10 MECHANICAL. | | 2) INDICATE HOW THE O/A DAMPER IS BEING CONTROLLED- | | REFER TO SECTION 503.2.5.4 FBC-10 ENERGY CONSERVATION. | | 3) THE TOILET EXHAUST FAN FOR BATH 1 SHALL HAVE A | | MINIMUM EXHAUST CAPACITY OF 100 CFM'S PER TABLE 403.3 | | FOOTNOTE E. 50 CFM PER TOILET OR URINAL. | | 4) PROVIDE TIE DOWN ENGINEERING FOR THE AC CONDENSERS- | | SECTION 301.12 | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|