Plan Review Notes
Plan Review Notes For Permit 15020941
Permit Number 15020941
Review Stop B
Sequence Number 2
Notes
Date Text
2015-06-25 16:24:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020941
 ADD: 633 5TH ST.
 CONT: BUILT SOLID CONSTRUCTION
 TEL: (561)333-2593
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 25/ 2015
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. MISSING SOILS REPORT WITH THE MINIMUM
 SAFE BEARING VALUE. 2010 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 3-8) COMPLIED.
  
 9) 2ND REQUEST. SHEET A-1 SHOWS A NEW RAMP WITH A
 HEIGHT OF 6 INCHES AND A 6 INCH STEP ADJACENT TO THE
 RAMP.THE 2010 FBC-B 1003.5 WHERE CHANGES IN ELEVATION
 OF LESS THAN 12 INCHES IN A MEANS OF EGRESS SLOPED
 SURFACES SHALL BE USED, NOT A STEP.
 NOTE IF THE FINISH FLOOR IS 6 INCHES OR LESS THAN
 HANDRAILS ARE NOT REQUIRED. IF WHEN IN THE FIELD THE
 RAMP IS EITHER GREATER THAN 6 INCHES IN HEIGHT OR 72
 INCHES IN LENGTH HANDRAILS WILL BE REQUIRED PER 1010.8
 WITH THE REQUIRED BACKING FOR HANDRAILS.
  
 10) 2ND REQUEST. SHEET A-1 SHOWS IN THE AREA OF WORK
 (2) EXTERIOR DOORWAYS WITH A 4INCH DROP, BOTH DOORS ARE
 SHOWN TO BE REQUIRED EXITS. PLEASE REVIEW:
 2010 FBC-B 1008.1.5 FLOOR ELEVATION. THERE SHALL BE A
 FLOOR OR LANDING ON EACH SIDE OF A DOOR. SUCH FLOOR OR
 LANDING SHALL BE AT THE SAME ELEVATION ON EACH SIDE OF
 THE DOOR. LANDINGS SHALL BE LEVEL EXCEPT FOR EXTERIOR
 LANDINGS, WHICH ARE PERMITTED TO HAVE A SLOPE NOT TO
 EXCEED 1 UNIT VERTICAL IN 50 UNITS HORIZONTAL
 (2-PERCENT SLOPE).
  
 11-14) COMPLIED.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]