Plan Review Notes
Plan Review Notes For Permit 15020941
Permit Number 15020941
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-02 07:00:571) SUBMIT DETAIL OF BREAKROOM SINK. SINK SHALL COMPLY
 W/ FAC SEC.212 & 606.
 2) SHOW THE DIMENSIONS ( L X W) OF THE TOILET ROOMS ON
 SHEET A-3.1.
 3) SHT. D-1 - THE BREAK ROON SINK COUNTERTOP SHALL BE
 AT A HEIGHT OF 34INCHES MAXIMUM ABOVE THE FINISH FLOOR
 PER THE 2010 FAC SEC.212 7 606.
 4) THE TOILET ROOMS DO NOT APPEAR TO BE WIDE ENOUGH TO
 PROVIDE THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE SPACING OF THE FIXTURES. A MINIMUM WIDTH
 OF 85 INCHES IS REQUIRED WHEN THE LAVATORY AND WATER
 CLOSET ARE ON THE SAME WALL. CLARIFY.
 5) SHT. A-1 - THE LOCATION OF THE URINAL IN THE MEN'S
 RESTROOM DOES NOT APPEAR TO PROVIDE THE REQUIRED
 PRIVACY AS SPECIFIED IN THE 2010 FPC SEC.310.5.THE LINE
 OF SIGHT TO THE URINAL WHEN THE DOOR IS OPEN IS CLEAR
 TO THE URINAL.
 6) SHT.A-3.1 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE OF THE GRAB BAR PER THE
 2010 FAC SEC.609.4. SEE DETAILS #2 & # 4 ON SHT. A3-1.
 7) SHT.A-3.1 - DETAIL #6 - THE LAVATORY CLEARANCES
 SHALL COMPLY WITH THE FAC SEC.606.3 (MAXIMUM 34" TO THE
 RIM OF THE LAVATORY).
 8) SHT. A-3.1 - DETAIL #8 SHOWS AN OPTIONAL CUP
 DISPENSER. THIS IS NOT PERMNITTED PER THE 2010 FAC
 SEC.211.2. A MINIMUM OF 2 DRINKING FOUNTAINS ARE
 REQUIRED.
 9) SHT. P-1 - ETAIL #3 - THE LAVATORY IN THE MEN'S
 RESSTROOM STALL IS NOT VENTED PER THE 2010 FPC
 SEC.901.2, 901.2.1.
 10) THE SANITARY SHOWS 3" VTR'S FOR 2" STACKS.LARIFY.
 11) THE URINAL IS NOT ON THE SANITARY RISER.
 12) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS.
 2010 FPC SEC.708.3.4.
 13) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND.
 TO 2010 FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  