2015-04-02 07:00:57 | 1) SUBMIT DETAIL OF BREAKROOM SINK. SINK SHALL COMPLY |
| W/ FAC SEC.212 & 606. |
| 2) SHOW THE DIMENSIONS ( L X W) OF THE TOILET ROOMS ON |
| SHEET A-3.1. |
| 3) SHT. D-1 - THE BREAK ROON SINK COUNTERTOP SHALL BE |
| AT A HEIGHT OF 34INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| PER THE 2010 FAC SEC.212 7 606. |
| 4) THE TOILET ROOMS DO NOT APPEAR TO BE WIDE ENOUGH TO |
| PROVIDE THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER |
| CLOSET AND THE SPACING OF THE FIXTURES. A MINIMUM WIDTH |
| OF 85 INCHES IS REQUIRED WHEN THE LAVATORY AND WATER |
| CLOSET ARE ON THE SAME WALL. CLARIFY. |
| 5) SHT. A-1 - THE LOCATION OF THE URINAL IN THE MEN'S |
| RESTROOM DOES NOT APPEAR TO PROVIDE THE REQUIRED |
| PRIVACY AS SPECIFIED IN THE 2010 FPC SEC.310.5.THE LINE |
| OF SIGHT TO THE URINAL WHEN THE DOOR IS OPEN IS CLEAR |
| TO THE URINAL. |
| 6) SHT.A-3.1 - THE GRAB BARS SHALL BE MEASURED TO THE |
| TOP OF THE GRIPPING SURFACE OF THE GRAB BAR PER THE |
| 2010 FAC SEC.609.4. SEE DETAILS #2 & # 4 ON SHT. A3-1. |
| 7) SHT.A-3.1 - DETAIL #6 - THE LAVATORY CLEARANCES |
| SHALL COMPLY WITH THE FAC SEC.606.3 (MAXIMUM 34" TO THE |
| RIM OF THE LAVATORY). |
| 8) SHT. A-3.1 - DETAIL #8 SHOWS AN OPTIONAL CUP |
| DISPENSER. THIS IS NOT PERMNITTED PER THE 2010 FAC |
| SEC.211.2. A MINIMUM OF 2 DRINKING FOUNTAINS ARE |
| REQUIRED. |
| 9) SHT. P-1 - ETAIL #3 - THE LAVATORY IN THE MEN'S |
| RESSTROOM STALL IS NOT VENTED PER THE 2010 FPC |
| SEC.901.2, 901.2.1. |
| 10) THE SANITARY SHOWS 3" VTR'S FOR 2" STACKS.LARIFY. |
| 11) THE URINAL IS NOT ON THE SANITARY RISER. |
| 12) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS. |
| 2010 FPC SEC.708.3.4. |
| 13) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. |
| TO 2010 FBC SEC. 107.3.5.1.3. |
| |