Plan Review Notes For Permit 15020941 |
Permit Number |
15020941 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-01 13:52:46 | PLANS DENIED | | 1) PROVIDE EXHAUST FOR BATHROOMS. PER TABLE 403.3 FBC | | (M) 2010 | | 2) PROVIDE OUTSIDE AIR DUCT ON PLANS WITH AUTOMATIC | | DAMPER. PER | | SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS FLORIDA | | ENERGY CODE | | 2010 FBC (M) | | 3) PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS ON | | AIR CONDITIONING | | EQUIPMENT. PER SECTION 304.1 GENERAL. | | 4) REFER TO SECTION 606.2.1 SUPPLY AIR, 606.3 | | INSTALLATION AND 606.4.1 SUPERVISION | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|