Plan Review Notes
Plan Review Notes For Permit 15020941
Permit Number 15020941
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-01 13:52:46PLANS DENIED
 1) PROVIDE EXHAUST FOR BATHROOMS. PER TABLE 403.3 FBC
 (M) 2010
 2) PROVIDE OUTSIDE AIR DUCT ON PLANS WITH AUTOMATIC
 DAMPER. PER
 SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS FLORIDA
 ENERGY CODE
 2010 FBC (M)
 3) PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS ON
 AIR CONDITIONING
 EQUIPMENT. PER SECTION 304.1 GENERAL.
 4) REFER TO SECTION 606.2.1 SUPPLY AIR, 606.3
 INSTALLATION AND 606.4.1 SUPERVISION
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676