2015-03-13 10:21:07 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15020941 |
| ADD: 633 5TH ST. |
| CONT: BUILT SOLID CONSTRUCTION |
| TEL: (561)333-2593 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| 1ST REVIEW |
| DATE: FRI. MARCH 13/ 2015 |
| ACTION: DENIED |
| |
| 1) THE ARCHITECT OF RECORD FOR THIS PROJECT HAS ON HER |
| TITLE BLOCK INDICATED THAT : DRAWINGS ARE SIGNED ND |
| SEALED FOR STRUCTURE ONLY. |
| DOES THE ARCHIEC TO RECORD HAVE A ENGINEERING LICENSE |
| AND REGISTRATION IN THE STATE OF FLORIDA? |
| ARCHITECTS SEAL 61G1-16.003 USE OF SEAL. |
| AN ARCHITECT OR INTERIOR DESIGNER SHALL NOT USE HIS |
| SEAL OR DO ANY OTHER ACT AS AN ARCHITECT OR INTERIOR |
| DESIGNER UNLESS HOLDING AT THE TIME A CERTIFICATE OF |
| REGISTRATION AND ALL REQUIRED RENEWALS THEREOF. |
| |
| 61G1-16.003 USE OF SEAL. |
| THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT |
| OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL |
| OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC |
| RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS |
| OR HIS CORPORATION. A CORPORATE SEAL ALONE IS |
| INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND |
| SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR |
| DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT |
| TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND |
| SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE |
| CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL |
| BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR |
| DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS |
| SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR |
| OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR |
| UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED |
| IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR |
| INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY |
| OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS |
| HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND |
| ALL REQUIRED RENEWALS THEREOF. |
| |
| ENGINEERING 471.003 471.003?QUALIFICATIONS FOR |
| PRACTICE; EXEMPTIONS. (3) HOWEVER, NO ENGINEER SHALL |
| PRACTICE ARCHITECTURE OR USE THE DESIGNATION |
| ?ARCHITECT? OR ANY TERM DERIVED THEREFROM, AND NO |
| ARCHITECT SHALL PRACTICE ENGINEERING OR USE THE |
| DESIGNATION ?ENGINEER? OR ANY TERM DERIVED THEREFROM. |
| |
| 2) MISSING SOILS REPORT WITH THE MINIMUM SAFE BEARING |
| VALUE. 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 3) THE ENERGY DOCUMENTS SUBMITTED SHOW A ELITE SOFTWARE |
| PROGRAM. UNDER THE 2010 FBC- ENERGY SHALL COMPLY WITH : |
| 103.2.1.2.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED COMMERCIAL BUILDING FORM 502 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| 103.2.2.2 SIMULATED PERFORMANCE ALTERNATIVE, COMMERCIAL |
| AND HIGH-RISE RESIDENTIAL. |
| AN ACCURATELY COMPLETED COMMERICAL BUILDING FORM 506 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) |
| DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR |
| COMPLIANCE BY SECTION 506. |
| 06.3.2 ENVELOPE LIMITATION. |
| FOR NEW BUILDINGS OR ADDITIONS, THE BUILDING ENERGY |
| COST BUDGET METHOD RESULTS SHALL NOT BE SUBMITTED FOR |
| BUILDING PERMIT APPROVAL TO THE CODE OFFICIAL PRIOR TO |
| SUBMITTAL FOR APPROVAL OF THE BUILDING ENVELOPE DESIGN. |
| |
| 4A) NOTE THE WINDOW AND DOOR PRODUCT APPROVALS |
| SUBMITTED, DOES NOT HAVE THE SHOP DRAWING STAMP OF |
| APPROVAL FROM THE DESIGNER OF RECORD. |
| SHOP DRAWING STAMP OF APPROVAL |
| 106.3* PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 4B) ROOFING PRODUCT APPROVAL, 2 DIFFERENT ROOFING |
| SHINGLE NOAS WERE SUBMITTED, NOA:14-1022.20 GAF |
| TIMBERLINE & NOA 11-0913.12 TAMCO ELITE GLASS-SEAL ROOF |
| SHINGLES. THE TAMCO ELITE SHINGLE DOES HAVE THE SHOP |
| DRAWING STAMP OF APPROVAL. WHICH IS TO BE INSTALLED? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 5) SHEET A-5 INDICATES THIS TO BE THE FOUNDATION PLAN. |
| THERE ARE NO NOTES IN REGARD TO THE MINIMUM BEARING |
| VALUE OF THE SOIL, VAPOR BARRIER REQUIREMENTS NOR THE |
| TYPE OF TERMITE TREATMENT FOR THE SLAB. |
| 1816.1 TERMITE PROTECTION. |
| 1910.1 MINIMUM SLAB PROVISIONS. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| SOIL CONDITIONS/ANALYSIS |
| TERMITE PROTECTION |
| DESIGN LOADS |
| WIND REQUIREMENTS |
| |
| 6) SHEET A-5 INDICATES IN A WALL SECTION SHEET S-1 |
| DETAIL 1 MISSING THERE IS NO S-1 SHEET. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 7) MISSING BEAM SCHEDULE, THE COLUMN SCHEDULE IS |
| PRINTED TWICE. NOT THERE IS ALSO NO LINTEL SCHEDULE FOR |
| WINDOWS NOR IS THERE A TRUSS LAYOUT WITH THE LOADS TO |
| BE RESISTED, GRAIVITY, UPLIFT OR LATERAL LOADS. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| DESIGN LOADS |
| WIND REQUIREMENTS |
| BUILDING ENVELOPE |
| WALL SYSTEMS |
| ROOF SYSTEMS TRUSSES, DROPPED TRUSSES FOR GABLE |
| OVERHANG OF 2 FT |
| MWFRS MAIN WIND FORCE RESISTING SYSTEM |
| |
| 8) THE COVERSHEET LIST THE NEW ADDITION AS A BUSINESS |
| OCCUPANCY. 2010 FBC-B 1004.1.1 AREAS WITHOUT SEATING |
| NEED TO BE EVALUATED IN THE WORST CASE SCENARIO, THIS |
| AREA MAY BE USED AS A SUNDAY SCHOOL CLASS, AS A |
| FELLOWSHIP HALL OR FOR OTHER FUNCTIONSOF A A3 |
| OCCUPANCY. SEE TABLE 1004.1.1 AREAS WHERE UN |
| CONCENTRATED SEATING TABLE AND CHAIRS PLEASE USE 15 |
| NET. |
| |
| 9) SHEET A-1 SHOWS A NEW RAMP WITH A HEIGHT OF 6 |
| INCHES. NOTE IF THE FINISH FLOOR IS 6 INCHES OR LESS |
| THAN HANDRAILS ARE NOT REQUIRED. IF WHEN IN THE FIELD |
| THE RAMP IS EITHER GREATER THAN 6 INCHES IN HEIGHT OR |
| 72 INCHES IN LENGTH HANDRAILS WILL BE REQUIRED PER |
| 1010.8 WITH THE REQUIRED BACKING FOR HANDRAILS. |
| |
| 10) SHEET A-1 SHOWS INTHE AREA OF WORK (2) EXTERIOR |
| DOORWAYS WITH A 4INCH DROP, BOTH DOORS ARE SHOWN TO BE |
| REQUIRED EXITS. NOTE WITH THE ASSEMBLY OCCUPANCY THIS |
| AREA WILL HAVE A OCCUPANT LOAD GREATERTHAN 50 REQUIRING |
| (2) EXITS. PLEASE REVIEW: |
| |
| 2010 FBC-B 1008.1.5 FLOOR ELEVATION. THERE SHALL BE A |
| FLOOR OR LANDING ON EACH SIDE OF A DOOR. SUCH FLOOR OR |
| LANDING SHALL BE AT THE SAME ELEVATION ON EACH SIDE OF |
| THE DOOR. LANDINGS SHALL BE LEVEL EXCEPT FOR EXTERIOR |
| LANDINGS, WHICH ARE PERMITTED TO HAVE A SLOPE NOT TO |
| EXCEED 1 UNIT VERTICAL IN 50 UNITS HORIZONTAL |
| (2-PERCENT SLOPE). |
| |
| 11) SHEET A-1 DOES NOT SHOW THE DOOR HARDWARE FOR THE |
| NEW DOOR OPENINGS. 2010 FBC-B 1008.1.9.1, 1008.1.9.3 |
| AND 1008.1.10. |
| |
| 12) SHEET A-2 INDICATES THE USE OF EAVE VENTS BUT DOES |
| NOT SHOW COMPLIANCE WITH THE UPPER PORTION OF THE ROOF |
| BEING VENTED. 2010 FBC-B 1203.2 ATTIC SPACES. THE NET |
| FREE VENTILATING AREA SHALL NOT BE LESS THAN 1/300 OF |
| THE AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF |
| THE REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS |
| LOCATED IN THE UPPER PORTION OF THE SPACE TO BE |
| VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR |
| CORNICE VENTS WITH THE BALANCE OF THE REQUIRED |
| VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| |
| 13) SHEET A-2 ALSO FAILS TTO SHOW COMPLIANCE WITH 2010 |
| FBC-B 1209.2 ATTIC SPACES. |
| AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| |
| 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: (561) 805-6715 |
| FAX: (561)805-6676 |
| E-MAIL: [email protected] |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| |
| |
| |
| |
| |
| |