Plan Review Notes
Plan Review Notes For Permit 15020937
Permit Number 15020937
Review Stop B
Sequence Number 9
Notes
Date Text
2017-06-21 09:16:05FBC 2014
 OCC CLASS 5TH ED E
 OCC LOAD 250
 PROP USE SCHOOL
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS 9
 FLOOD ZONE A5 7.00
 UNITS 1
 FLOORS 2
 BEDROOMS 0
 SQ FT LIVABLE 16033
 SQ FT FOOTPRINT 8736
 SQ FT ROOF 7260
 USC-404 TYPE 326 - NEW:SCHOOL OR UNIVERSITY
  
 DFE PER PLAN = 8.96' NGVD29
  
 BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE OR
 FORM BOARD SURVEY SHOWING PROPOSED ELEVATIONS IS
 REQUIRED PRIOR TO CONCRETE POUR
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS REQUIRED
 PRIOR TO FINAL INSPECTION.
  
 PROPOSED STRUCTURE IS LOCATED IN SFHA A5. THE FIRST
 FLOOR PROPOSED FFE IS 8.46
  
 ELEVATION CERTIFICATE / FORM BOARD SURVEY REQUIRED
 PRIOR TO CONCRETE POUR
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE REQUIRED
 PRIOR TO FINAL INSPECTION
  
  
  
  