2016-12-02 17:41:341ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE BATHROOMS IN THE CLASS ROOMS ON FIRST FLOOR
 SHOULD COMPLY WITH THE REQUIREMENTS FOR THE YOUNGER
 CHILDREN IN THE ADVISORY CHART FBC ACC 604.9
  
 2. THE RIM OF LAVATORY'S IN ALL THE CHILDREN'S
 BATHROOMS SHOULD BE SET AT 31" ABOVE FINISHED FLOOR.
 PER FBC ACC 606.2
  
 3. SEPARATE FACILITIES FOR EACH SEX ARE REQUIRED FOR
 THE STAFF BATHROOMS. PER FBC PL 403.2
  
 4. SHT. A4.2 DETAIL 03 PLEASE PROVIDE THE DIMENSION
 FROM THE SIDE WALL OF TOILET TO THE PARTITION NEXT TO
 LAV IT SHALL BE A MIN OF 84" 85 " TO ALLOW FOR
 CONSTRUCTION TOLERANCES. PER FBC PL 604.3.1
  
 5. SHT. A4.2 DETAIL 01 THE WIDTH OF 6' 8" DOES NOT
 ALLOW FOR COMPLIANCE WITH FBC PL 604.3.1 IT SHALL BE
 84" 85 " TO ALLOW FOR CONSTRUCTION TOLERANCES.
  
 6.SHT A4.2 DETAIL 04 PROVIDE DIMENSION FROM SIDEWALL OF
 TOILET TO THE PARTITION TO COMPLY WITH FBC PL604.3.1
  
 7. SHT. 3.1 SANITARY RISER
 A) FIRST FLOOR RM 180 THE FLOOR DRAIN SHALL BE
 INDIVIDUALLY VENTED. PER FBC PL 901.2 AND 901.2.1
 B)FIST FLOOR RM 181 THE FLOOR DRAIN SHALL CONNECT WITH
 FIXTURE BRANCH OF SERVICE SINK NO BUILDING DRAIN. PER
 FBC PL 901.2 AND 901.2.1
 C)SECONDD FLOOR IN ROOM 280 THE FLOOR DRAIN SHALL BE
 INDIVIDUALLY VENTED. PER FBC PL 901.2 AND 901.2.1
 D) SECON FLOOR THE EWC SHALL CONNECT DOWN STREAM OF THE
 BATHROOM GROUPS.FBC PL 909.1
  
 8 SHT. P8.1 DETAIL 7 THE HOT WATER RECIRCULATION RETURN
 LINE SHALL CONNECT TO COLD WATER INLET OF WATER HEATER
 AND THE TEMPERING VALVE. PER FBC PL 607.2.3
  
 9. SHT.P5.1 ROOF AREAS G,F,I,J HAVE A NOTE ON THEM THAT
 STATES HORIZONTAL STORM DRAIN SIZE = 3" 657 SF MAX THIS
 IS UNDER THE SF OF THESE AREAS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 10. SHT. P5.1 THE OVERFLOW DRAIN SHALL BE SIZED THE
 SAME AS THE PRIMARY DRAIN. PER FBC PL 1107.3
  
 11. PLEASE PROVIDE SF AND SLOPE ON THE STORM RISER
 DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
 12. SHT. P6.1 DETAIL 1 THE NOTE ON 1" CD DN TO FIRST
 FLOOR SHOULD READ DN FROM 2ND FLOOR PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 13. ARE ANY OF THE CLASSROOMS BEING USED AS A SCIENCE
 LAB THAT WILL USW CHEMICALS IF SO PLEASE PROVIDE TYPE
 OF CHEMICAL MSDS SHEETS THE AMOUNTS AND HOW THERE BEING
 STORED. PER WPB AMEND TO FBC 107.2.1
  
  