Plan Review Notes
Plan Review Notes For Permit 15020937
Permit Number 15020937
Review Stop M
Sequence Number 4
Notes
Date Text
2016-12-15 11:44:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #15020937
 12/15/16
  
 1) PLEASE CLARIFY OR CORRECT THE FOLLOWING CONFLICTS
 CONCERNING THE HEATING CAPACITIES FOR THE AHU'S:
  
 A) THE ENERGYGAUGE COMPLIANCE DATA FORM INDICATES
 136520 BTUH ELECTRIC FURNACE CAPACITIES FOR AHU 1-1 AND
 1-2 , HOWEVER NO ELECTRIC DATA IS LISTED IN THE
 SCHEDULES FOR THE UNITS ON M4.2, AND DUCT HEATERS AT 40
 KW EACH ARE SPECIFIED FOR BOTH SYSTEMS.
  
 B) THE AC LOAD CALCULATIONS INDICATE 87,461 BTUH
 (25.6KW) HEATING REQUIRED FOR AHU 1-1, AND 24,624 BTUH
 (7.2KW) FOR AHU 1-2 WHICH INDICATES THE DUCT HEATERS
 HAVE BEEN OVERSIZED.
  
 C) THE HEATING CAPACITIES FOR AHU'S 1-4 & 2-1 ARE
 OVERSIZED BASED ON THE CALCULATED LOADS.
  
 2) PROVIDE COMPLIANCE DATA FOR THE CHILLER IN THE
 ENERGYGAUGE SUBMITTAL- SEE TABLE C403.2.3(7) FBC-14
 ENERGY CONSERVATION.
  
 3) M5.2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 ATTACHMENT OF THE CHILLER- SEE SECTION 301.15.
  
 4) PROVIDE WIND LOAD ENGINEERING AND DESIGN CRITERIA
 FOR ATTACHMENT OF THE ROOFTOP FGI GRAVITY INTAKE HOOD.
  
 5) SHOW THE REQUIRED CLEARANCES FOR THE GRAVITY INTAKE
 ON THE ROOF PER SECTION 401.4, AND INDICATE HOW THE
 OPENING WILL BE PROTECTED PER SECTION 401.5.
  
 6) INDICATE THE REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS FOR THE EXHAUST OUTLETS PER SECTION
 501.3.1 AND SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE LOUVER- RULE 9N-3 DEPT. OF COMMUNITY
 AFFAIRS.
  
 7) PROVIDE SUBMITTALS FOR THE FIRE DAMPERS AND O/A
 MOTORIZED DAMPERS, AND PROVIDE INSTALLATION DETAILS ON
 THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  