Date |
Text |
2016-11-21 15:48:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET LS 1.1 & OTHER A SHEETS - EXIT STAIR 1-003 |
| INDICATES AN EXITING DOOR ON THE GROUND LEVEL. THERE IS |
| AN SLIDING GLASS DOOR ASSEMBLY LOCATED WITHIN 10FT THAT |
| IS NOT INDICATED A FIRE RATED. |
| |
| PER NFPA 101, CHAPTER 7 |
| |
| 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| 7.2.2.5.1 ENCLOSURES. |
| 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH |
| 7.1.3.2. |
| |
| 7.2.2.5.2* EXPOSURES. |
| 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED |
| OPENINGS ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER THAN |
| AN EXISTING STAIRWAY, AND THE WALLS OR OPENINGS ARE |
| EXPOSED BY OTHER PARTS OF THE BUILDING AT AN ANGLE OF |
| LESS THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS |
| WITHIN 10 FT (3050 MM) HORIZONTALLY OF THE NONRATED |
| WALL OR UNPROTECTED OPENING SHALL BE CONSTRUCTED AS |
| REQUIRED FOR STAIRWAY ENCLOSURES, INCLUDING OPENING |
| PROTECTIVES. |
| 7.2.2.5.2.2 CONSTRUCTION SHALL EXTEND VERTICALLY FROM |
| THE FINISHED GROUND LEVEL TO A POINT 10 FT (3050 MM) |
| ABOVE THE TOPMOST LANDING OF THE STAIRS OR TO THE |
| ROOFLINE, WHICHEVER IS LOWER. |
| 7.2.2.5.2.3 THE FIRE RESISTANCE RATING OF THE |
| SEPARATION EXTENDING 10 FT (3050 MM) FROM THE STAIRS |
| SHALL NOT BE REQUIRED TO EXCEED 1 HOUR WHERE OPENINGS |
| HAVE A MINIMUM ?-HOUR FIRE PROTECTION RATING. |
| |
| PLEASE PROVIDE FOR THE REQUIRED RATING. |
| |
| |
| 2) SHEET LS 1.2 & OTHER A SHEETS - THERE ARE WINDOWS |
| INDICATEDAS "J" WITHIN THE EXIT ENCLOSURES 1-003 & |
| 1-006. THOSE WINDOWS CAN NOT BE FOUND ON THE SCHEDULE |
| AS HAVING ANY KIND OF FIRE RATING THAT IS EQUAL TO THE |
| WALL RATING. |
| |
| PER NFPA 101, CHAPTER 7 |
| |
| 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| 7.2.2.5.1 ENCLOSURES. |
| 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH |
| 7.1.3.2. |
| |
| 7.1.3.2 EXITS. |
| 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE |
| SEPARATED FROM OTHER PARTS OF THE BUILDING, THE |
| SEPARATING CONSTRUCTION SHALL MEET THE REQUIREMENTS OF |
| SECTION 8.2 AND THE FOLLOWING: |
| (1)* THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE |
| RESISTANCE RATING WHERE THE EXIT CONNECTS THREE OR |
| FEWER STORIES. |
| |
| (9)* OPENINGS IN EXIT ENCLOSURES SHALL BE LIMITED TO |
| DOOR ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND |
| CORRIDORS AND DOOR ASSEMBLIES FOR EGRESS FROM THE |
| ENCLOSURE, UNLESS ONE OF THE FOLLOWING CONDITIONS |
| EXISTS: |
| |
| (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT |
| ENCLOSURE |
| ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING: |
| |
| A WINDOW IS NOT LISTED UNDER ANY OF THE 9 ITEMS. |
| |
| THE WINDOW OPENING SHALL BE RATED OR REMOVED AS IT IS |
| NOT ESSTENITIAL FOR THE FUNCTION OF THE STAIR. |
| |
| |
| |
| 3) LS 1.1 - THE WALLS SURROUNDING THE STORAGE ROOM |
| 1-111 ARE NOT INDICATED AS BEING FIRE RATED EQUAL TO |
| THE STAIR ENCLOSURE. |
| |
| 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN |
| EXIT ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER |
| STAIRS, UNLESS OTHERWISE PERMITTED BY 7.2.2.5.3.2. |
| 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED |
| UNDER STAIRS, PROVIDED THAT BOTH ALL OF THE FOLLOWING |
| CRITERIA ARE MET: |
| (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR |
| ENCLOSURE BY THE SAME FIRE RESISTANCE AS THE EXIT |
| ENCLOSURE. |
| (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE |
| FROM WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.) |
| (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE, |
| OR OTHERWISE HAZARDOUS MATERIALS. |
| |
| PLEASE PROVIDE DETAIL FOR THIS REQUIREMENT |
| |
| |
| |
| 4) SHEET A 19.1 & A 14.1 - THE SHEETS WERE PLACED |
| UPSIDE DOWN. |
| |
| PLEASE CORRECT TO PROPER PLACEMENT. |
| |
| |
| |
| 5) SHEET A 14.1 - THE DOOR SCHEDULE APPEARS TO ONLY |
| INDICATED DOORS ON THE 2ND LEVEL, THERE APPEARS TO BE |
| NO DOOR SCHEDULE FOR THE 1ST FLOOR. |
| |
| PLEASE REVIEW AND ENSURE THE IS A DOOR SCHEDULE FOR THE |
| 1ST FLOOR AND ALL DOORS ARE ACCOUNTED FOR. |
| |
| |
| |
| 6) SHEET A 14.1 - DOORS , BUT NOT LIMITED TO, 203, 008, |
| 200, 206A, 206(STAFF LOUNGE) 003, ALL APPEAR TO BE |
| MISSING FROM THE SCHEDULE. |
| |
| PLEASE REVIEW ALL DOORS AND ENSURE THEY ARE CONTAINED |
| WITHIN THE DOR SCHEDULE. |
| |
| |
| |
| |
| 7) LS 1.2 - THERE ARE MULTIPLE CANOPY'S THAT COVER THE |
| EXIT EGRESS TO A PUBLIC WAY. THESE CANOPY'S ARE |
| INDICATED WITH ANY FIRE PROTECTION RATING OR FIRE |
| SPRINKLER PROTECTION. |
| |
| PER NFPA 101 EXIT DISCHARGE SHALL BE PROVIDED TO A |
| PUBLIC WAY. |
| |
| 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF |
| EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC |
| WAY. |
| |
| 7.1.9 IMPEDIMENTS TO EGRESS. ANY DEVICE OR ALARM |
| INSTALLED TO RESTRICT THE IMPROPER USE OF A MEANS OF |
| EGRESS SHALL BE DESIGNED AND INSTALLED SO THAT IT |
| CANNOT, EVEN IN CASE OF FAILURE, IMPEDE OR PREVENT |
| EMERGENCY USE OF SUCH MEANS OF EGRESS, UNLESS OTHERWISE |
| PROVIDED IN 7.2.1.6 AND CHAPTERS 18, 19, 22, AND 23. |
| |
| 7.1.10 MEANS OF EGRESS RELIABILITY. |
| 7.1.10.1* GENERAL. MEANS OF EGRESS SHALL BE |
| CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTIONS OR |
| IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF FIRE OR |
| OTHER EMERGENCY. |
| |
| 7.2.3.5 DISCHARGE. |
| 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| INTO A PUBLIC WAY, INTO A YARD OR COURT HAVING DIRECT |
| ACCESS TO A PUBLIC WAY, OR INTO AN EXIT PASSAGEWAY. |
| SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT OPENINGS, OTHER |
| THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE |
| DOOR OPENING TO THE OUTSIDE YARD, COURT, OR PUBLIC WAY. |
| THE EXIT PASSAGEWAY SHALL BE SEPARATED FROM THE |
| REMAINDER OF THE BUILDING BY A 2-HOUR FIRE RESISTANCE |
| RATING. |
| |
| PROTECTION SHALL BE PROVIDED UNTIL A PERSON HAS ACCESS |
| TO A PUBLIC WAY. THE CANOPY STRUCTURE CAN BE AFFECTED |
| BY THE PRODUCTS OF COMBUSTION WHICH COULD LEAD TO |
| FAILURE AND TRAP EXTING PERSONS. |
| |
| PLEASE PROVIDE FOR THE REQUIRED PROTECTION LEADING TO A |
| PUBLIC WAY. |
| |
| |
| |
| 8) SHEET S 6.1 - THERE APPEARS TO BE LIGHT WEIGHT TRUSS |
| CONSTRUCTION OF BOTH THE FLOOR AND ROOF OF THE PROPOSED |
| BUILDING. |
| |
| PLEASE PROVIDE FOR THE APPLICABLE FLOOR & TRUSS SIGN |
| REQUIRED BY FLORIDA STATUTUE. |
| |
| PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| THE LEFT OF THE MAIN ENTRY DOOR. |
| 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| MARKED WITH THE LETTER "R". |
| 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| SHALL BE MARKED WITH THE LETTER "F". |
| 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| |
| |
| |
| 9) SHEETS LS 1.1 & LS 1.2 - A KITCHEN IS INDICATED |
| WITHIN THE NOTES OF THE LIFE SAFETY PLAN. |
| |
| PER NFPA 101, CHAPTER 14, NEW EDUCATIONAL OCCUPANCIES |
| |
| 14.3.2.2 COOKING FACILITIES SHALL BE PROTECTED IN |
| ACCORDANCE WITH 9.2.3. OPENINGS SHALL NOT BE REQUIRED |
| TO BE PROTECTED BETWEEN FOOD PREPARATION AREAS AND |
| DINING AREAS. |
| |
| 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING |
| EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD |
| FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| COMMERCIAL COOKING OPERATIONS, UNLESS SUCH |
| INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE. |
| |
| PLEASE PROVIDE DETAILS AND THE LOCATION OF THE TYPE OF |
| KITCHEN BEING PROPOSED. |
| |
| |
| |
| 10) SHEETS LS 1.1 & 1.2 - SCIENCE LAB IS INDICATED |
| WITHIN THE NOTES OF THE LIFE SAFETY PLAN. |
| |
| 14.3.2.5 EDUCATIONAL OCCUPANCY LABORATORIES USING |
| CHEMICALS SHALL BE IN ACCORDANCE WITH 8.7.4. |
| |
| 8.7.4 LABORATORIES. |
| 8.7.4.1 LABORATORIES THAT USE CHEMICALS SHALL COMPLY |
| WITH NFPA 45, STANDARD ON FIRE PROTECTION FOR |
| LABORATORIES USING CHEMICALS, UNLESS OTHERWISE MODIFIED |
| BY OTHER PROVISIONS OF THIS CODE. |
| |
| PLEASE PROVIDE DETAILS AND THE LOCATION OF THE SCIENCE |
| LAB BEING PROPOSED. |
| |
| |
| |
| 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |