Plan Review Notes
Plan Review Notes For Permit 15020937
Permit Number 15020937
Review Stop M
Sequence Number 2
Notes
Date Text
2015-09-09 15:45:422ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15020937
 9/9/2015
  
 1) PROVIDE AC COOLING AND HEATING LOAD CALCULATIONS FOR
 THE CHILLER, AHU'S, FCU'S, & AHU/CU 1 & 2. REFER TO
 SECTION 503.2.1 FBC-10 ENERGY CONSERVATION: CALCULATION
 OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION 501.2 FBC-10 ENERGY CONSERVATION. SUBMIT TWO
 COPIES OF FORM 502 FOR PRESCRIPTIVE COMPLIANCE, OR FORM
 506 FOR PERFORMANCE BASED COMPLIANCE USING COMMISION
 APPROVED SOFTWARE PRINTOUT.
 4) SHEET M0.1: APPLICABLE BUILDING CODES SHALL ALSO
 INCLUDE THE FBC-10 ENERGY CONSERVATION CODE. PLEASE
 REVIEW AND REVISE.
 5) SHEET M0.1: THE VENTILATION CALCULATION TABLE IS NOT
 INDICATING ANY O/A CFM'S FOR THE CORRIDOR. PER TABLE
 403.3, VENTILATION SHALL BE PROVIDED AT .06 CFM'S PER
 SQ. FT. PLEASE REVISE THE TABLE ACCORDINGLY.
 6) M2.1: DAMPERS MISSING AT THESE LOCATIONS- A) 18"X14"
 DUCT PENETRATING RATED WALL BETWEEN CORRIDOR 1-002 AND
 ROOM 1-111. B) 8" ROUND DUCT PENETRATING RATED WALL
 BETWEEN CORRIDOR 1-002 AND ROOM 1-111A. C) 12"X12" DUCT
 PENETRATING RATED WALL BETWEEN CORRIDOR 1-009 & ROOM
 1-201.
 7) M2.2: DAMPERS MISSING AT THESE LOCATIONS- A) 14"X14"
 DUCT PENETRATING THE RATED WALL BETWEEN CORRIDOR 1-006
 AND ROOM 1-202. B) 8" ROUND DUCT PENETRATING THE RATED
 WALL BETWEEN ROOM 1-202 AND CORRIDOR 1-009.
 8) M2.1 & M2.2: PLEASE CLARIFY WHY ALL OF THE AC DUCTS
 PENETRATING THE SMOKE PARTITIONS ON THE PLANS HAVE
 SMOKE DAMPERS BUT NONE OF THE EXHAUST DUCTS PENETRATING
 THOSE WALLS HAVE DAMPERS.
 9) M2.3: THE CHILLER DETAIL IS REFERENCING THE
 STRUCTURAL PLANS FOR ANCHORING THE UNIT, HOWEVER THE
 DETAIL ON SHEET S-4.3 DOES NOT INDICATE HOW THE CHILLER
 IS TO BE TIED DOWN TO THE CURB. PLEASE REVISE THE
 DETAIL.
 10) M2.3: PROVIDE WINDLOAD TIE DOWN ENGINEERING FOR
 ANCHORING THE DUCT STANDS- SECTION 301.12 FBC-10
 MECHANICAL.
 11) M6.1: PROVIDE A NARRATIVE TO CLARIFY HOW THE
 DIGITAL CONTROL SYSTEM WILL FUNCTION WITH THE HVAC
 SYSTEM- REFER TO SECTION 503.2.4 FBC-10 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  