Date |
Text |
2015-10-05 16:03:59 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15020937 |
| ADD: 1901 S. FLAGLER DR. |
| CONT: IBIS BUILDING CORP. |
| TEL: (561)318-8408 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| 2ND REVIEW |
| DATE: MON. OCT. 05 / 2015 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THIS PROJECT WILL REQUIRE A RESIDENT |
| INSPECTOR. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 |
| POUNDS PER SQUARE INCH |
| 4. FOR PILE DRIVING |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION |
| |
| 1A) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 1B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| [email protected] |
| |
| 1C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED INCLUDING SOILS REPORTS, ENERGY CALCS AND |
| PRODUCT APPROVALS. FOR DIGITAL PLANS, AFTER PERMIT |
| ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS. |
| |
| 1D) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 2)PROVISO: NOTICE: ART IN PUBLIC PLACES |
| |
| THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL |
| PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| |
| 3)2ND REQUEST. FLOOD ZONE CERTIFICATES |
| FBC BUILDING SECTION 1612 AND CITY OF WPB CODE OF |
| ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| "A5" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE |
| REQUIRED. PLEASE REVIEW CITY ORDINANCE FOR THE CITY |
| REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF |
| ELEVATION MINIMUM. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH |
| FLOOR HEIGHT. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS A/C PADS OR OTHER SLABS FOR |
| GENERATORS. |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: JULY 31/2015. |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 4) 2ND REQUEST. MISSING SOILS REPORT, WILL REQUIRE 3 |
| ORIGINALS FOR PAPER PLANS. FBC-B 1803.5.2 QUESTIONABLE |
| SOIL. |
| WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED.5) THE PERMIT |
| APPLIED VALUE IS STATED AS $4,055,000 THE CALCULATED |
| VALUE IS $4,131,694.00 IN VALUE. W P B ADMINISTRATIVE |
| CODE 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS, |
| STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND PLUMBING |
| SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR |
| EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE |
| WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE |
| GOVERNING AUTHORITY. |
| |
| |
| 5) COMPLIED> ADJUSTED VALUE TO CALCULATED VALUE. THE |
| PERMIT APPLIED VALUE IS STATED AS $4,055,000 THE |
| |
| 6-7) COMPLIED |
| 8) SEMI-COMPLIED. RESPONSE INDICATED ROOM 1-0004. SHEET |
| LS 1.1 ROOMS 1-104 (COMPLIED 1-190) ARE MISSING THE |
| EXIT SIGNS TO BE LOCATED AT THE EXIT DOORWAY OF THE |
| ROOM, FBC-B 1006.3.8. |
| |
| 9-12) COMPLIED. |
| |
| 13) SEMI-COMPLIED. SHEET A8.4 COMPLIES, THE ISSUE IS |
| WITH SHEET A5.2 DETAIL 01 HAS HORIZONTAL MULLIONS, THE |
| HORIZONTAL MULLIONS DOESN?T WORK WITH WATER CURTAINS. |
| SHEET LS 1.2 SHOWS AN 2 STORY ATRIUM ON THE SECOND |
| FLOOR BUT THERE IS NO ENCLOSURE AROUND THE ATRIUM NOR |
| COMPLIANCE WITH FBC-B 404.6 ENCLOSURES OF ATRIUMS OR |
| EXCEPTIONS. |
| |
| 14) COMPLIED . VERTICAL ACCESSIBILITY. |
| |
| 15-223B) COMPLIED |
| 23C) SEMI-COMPLIED. ROOF PRESSURES ARE GOOD. THE VULT |
| NEGATIVE PRESSURES ARE LOW IN WALL ZONES 4 AND 5 |
| NEGATIVE PRESSURES ARE TAKEN AT THE ROOF LEVEL. SINCE |
| THE VULT ARE LOW ALL OF THE NEGATIVE VASD ARE LOW. |
| SHEET S6.1 ELEVATIONS WITH ASSOCIATED PRESSURES WILL |
| NEED TO BE WORKED TO REFLECT THE 180 VULT, EXPOSURE D |
| AND MEAN ROOF HEIGHT OF 28.33 FT. PLEASE SHOW PRESSURES |
| IN VASD SINCE THE PRODUCT APPROVALS ARE LISTED IN VASD. |
| FBC-B 1609.1.5 TESTING TO ALLOWABLE OR NOMINAL LOADS. |
| 23D-25) COMPLIED. |
| |
| 26) PROVISO: SHEET S 7-3. FOR PROPOSED ALUMINUM |
| TRELLIS/ CANOPY SYSTEM THE DELEGATE ENGINEER IS TO |
| SUBMIT SHOP DRAWINGS FOR APPROVAL TO THE ENGINEER OF |
| RECORD FOR REVIEW AND APPROVAL BEFORE SUBMISSION TO THE |
| BUILDING DEPARTMENT. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| |
| |
| 27) PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (F) SKYLIGHTS |
| G) ROOF TOP CURBS/ PRE- MANUFACTURED A/C STANDS |
| 28) PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 29) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 30) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |