Plan Review Notes For Permit 15020937 |
Permit Number |
15020937 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-20 14:03:07 | ROOF SUB PERMIT REQUIRED | | | | PRODUCT APPROVALS FOR ROOF SYSTEM (METAL DECK, R19 | | TAPERED INSULATION AND CONCRETE DECK, R19 TAPERED | | INSULATION, PREFAB SKYLIGHT SYSTEM) REVIEWED BY DOR IS | | REQUIRED TO BE SUBMITTED FOR PERMIT PRIOR TO | | INSTALLATION. | | | | ROOF COMPONENTS & CLADDING TO COMPLY WITH DESIGN | | PRESSURES SPECIFIED ON SHEET S6.1: | | | | VULT (MULTIPLY BY .6) | | | | ZONE 1, -95.6 | | ZONE 2, -160.30 | | ZONE 3, -241.3 | | | | | | |
|