2015-04-01 12:29:311) LIFE SAFETY SHEETS - THE BUILDING INFORMATION BOX
 SHOWS THE OCCUPANCY REQUIREMENTS FOR EDUCATION AT 20
 SQUARE FEET PER PERSON YET LIFE SAFETY PLAN LS1.1 SHOWS
 THE OCCUPANT LOAD AS 35 SQUARE FEET PER PERSON. CLARIFY
 AND ENSURE THAT THE OCCUPANT LOADS OF THE AREAS ARE
 BASED ON TABLE 1004.1.1 OF THE 2010 FBC.
 2) SHT. T1 & PLUMBING SHEETS OF THE PLANS I REVIEWED
 REFER TO CIVIL DRAWINGS. THERE WERE NO CIVIL DRAWINGS
 IN THE SET OF PLANS I REVIEWED. CLARIFY.
 3) SHT.LS 1.2 IS MISSING FORM THE SET OF PLANS I
 REVIEWED. SUBMIT SHEET FOR REVIEW.
 4) SHT. A8.2 - ENLARGED RESTROOM PLANS 02 03, 04, DO
 NOT COMPLY WITH THE 2010 FL. ACCESSIBILITY CODE SEC.
 604.3, 606. THE MINIMUM REQUIRED WIDTH IS 85" IF BUILT
 PERFECT. 86 INCHES ALLOWS FOR CONSTRUCTION TOLERANCES.
 5) SHT. A8.2 - DETAIL # 06 - IT APPEARS THAT THE DOOR
 MAY SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY
 IN ACCESSIBLE STALL IN THE MALE AND FEMALE RESTROOM.
 FAC SEC.604.8.1.2.
 6) CLEARLY SHOW THE DIMENSIONS OF THE LENGTH AND WIDTH
 OF THE CLEAR FLOOR SPACES FOR THE LAVATORIES AND THE
 WATER CLOSETS IN THE ACCESSIBLE TOILET COMPARTMENTS AND
 TOILET ROOMS. FAC SECS.604.3 & 606.2.
 7) VERTICAL ACCESSIBILITY IS REQUIRED TO THE SECOND
 FLOOR PER THE 2010 FAC SEC.201.1.1.
 8) FLOOR DRAINS AND HOSE BIBBS ARE REQUIRED IN THE
 GROUP TOILET ROOMS PER THE 2010 FBC SEC.443.3.5.6.
 9) SHT. P4.1 - CLINIC RESTROOM - THERE IS AN ARROW THAT
 POINTS TO "2 " SANITARY UP" BUT NOTHING IS SHOWN.
 CLRIFY.
 10) SHT.P4.1 - ADULT RESTROOM # 1-103 - THE LAYOUT ON
 THE RISER DOESN'T CORRELATE WITH THE FLOOR PLAN.
 CLARIFY.
 11) SHT. P4.1 - THE 2" LINE ON RISER BY EWC SAYS 2"
 SANITARY UP BUT IS NOT CONNECTED TO THE BUILDING DRAIN
 & TERMINATES NOWHERE. CLARIFY.
 12) SHT. P4.1 - A WATER CLOSET IS MISSING FROM THE
 RISER FOR TOILET ROOMS 1-106 & 1-107A.
 13) THE SANITARY RISER APPEARS TO MISSING PIPING FROM
 RESTROOMS 106-A & 107-A.
 14) SHT. P4.1 - SINK SK-1 IN THE ART LAB IS NOT
 CONNECTED TO THE SANITARY SYSTEM.
 15) SUBMIT SPECIFICATIONS ON THE SOLIDS INTERCEPTOR
 ZURN ZA - 1184. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SHT. P4.1 - SIZE THE VENT FOR SINK SK-1 IN THE ART
 LAB.
 17) SHT.P4.1 - THE ARE NUMEROUS SECTIONS OF THE
 SANITARY RISER WHERE PIPNG HAS NO CONNECTION POINTS AND
 TERMINATES NOWHERE. SUBMIT A SANITARY RISER DIAGRAM
 THAT CLEARLY REFLECTS ALL AREAS OF THE INSTALLATION.
 EXPAND THE CONDENSED AREAS OF THE RISER DIAGRAM SO IT
 IS CLEAR AND LEGIBLE. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 18) SHT. P4.1 - PLUMBING FIXTURE SCHEDULE - THE MINIMUM
 TRAP SIZE FOR SINKS SHALL BE 1 1/2" NOT 1 1/4" AS SHOWN
 PER FPC TABLE 709.1.
 19) SHT. P4.2 - SIZE ALL SECTIONS OF THE WATER RISER.
 WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 20) SHT. P4.2 HAS NOTATION "WC-1" BUT NOTHING IS SHOWN.
 REFER TO SHT. P3.1 FOR LOCATION. SEE AREA BY GRID LINE
 H11.
 21) SIZE THE WATER RISERS TO THE 2ND FLOOR.
 22) SHT. P5.3 - A COMPLETE AND THOROUGH REVIEW CANNOT
 BE ACCOMPLISHED ON THE STORMWATER RISER BECAUSE IT IS
 INCOMPLETE; LINES TERMINATE NOWHERE, LINES ARE MISSING,
 ETC. SUBMIT A COMPLETE, CLEAR AND LEGIBLE STORMWATER
 RISER DIAGRAM FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 23) SHT. P5.2 - THE DESIGN OF THE STORMWATER SYSTEM
 SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT
 DIVERTS WATER TO THE ROOF. SHOW THAT THE AREA OF THE
 PARAPET WALL HAS BEEN ADDED INTO THE STORMWATER DESIGN
 PER THE 2010 FPC SEC.1106.4.
 24) SHT. P7.1 - THE PLAN SHOWS THE WATER HEATER BEING
 BOTTOM FED BY THE RECIRCULATING LINE. A VACUUM RELIEF
 VALVE IS REQUIRED ON THIS LINE PER SEC. 504.2 OF 2010
 FPC.
 25) SHT. P7.2 - THE DOMESTIC WATER DEMAND TABLE REFERS
 TO TABLE E103.2(2). THERE IS NO SUCH TABLE . CLARIFY.
 26.) DOES THIS SCHOOL ALSO HAVE DAYCARE OR WILL IT BE
 USED AS A DAYCARE FACILITY AT ANY TIME? DAYCARE
 FACILITIES SHALL COMPLY W/ 2010 FBC SEC. 436.
  
  
 PLUMBING PLAN REVIEW