2015-04-01 12:29:31 | 1) LIFE SAFETY SHEETS - THE BUILDING INFORMATION BOX |
| SHOWS THE OCCUPANCY REQUIREMENTS FOR EDUCATION AT 20 |
| SQUARE FEET PER PERSON YET LIFE SAFETY PLAN LS1.1 SHOWS |
| THE OCCUPANT LOAD AS 35 SQUARE FEET PER PERSON. CLARIFY |
| AND ENSURE THAT THE OCCUPANT LOADS OF THE AREAS ARE |
| BASED ON TABLE 1004.1.1 OF THE 2010 FBC. |
| 2) SHT. T1 & PLUMBING SHEETS OF THE PLANS I REVIEWED |
| REFER TO CIVIL DRAWINGS. THERE WERE NO CIVIL DRAWINGS |
| IN THE SET OF PLANS I REVIEWED. CLARIFY. |
| 3) SHT.LS 1.2 IS MISSING FORM THE SET OF PLANS I |
| REVIEWED. SUBMIT SHEET FOR REVIEW. |
| 4) SHT. A8.2 - ENLARGED RESTROOM PLANS 02 03, 04, DO |
| NOT COMPLY WITH THE 2010 FL. ACCESSIBILITY CODE SEC. |
| 604.3, 606. THE MINIMUM REQUIRED WIDTH IS 85" IF BUILT |
| PERFECT. 86 INCHES ALLOWS FOR CONSTRUCTION TOLERANCES. |
| 5) SHT. A8.2 - DETAIL # 06 - IT APPEARS THAT THE DOOR |
| MAY SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| IN ACCESSIBLE STALL IN THE MALE AND FEMALE RESTROOM. |
| FAC SEC.604.8.1.2. |
| 6) CLEARLY SHOW THE DIMENSIONS OF THE LENGTH AND WIDTH |
| OF THE CLEAR FLOOR SPACES FOR THE LAVATORIES AND THE |
| WATER CLOSETS IN THE ACCESSIBLE TOILET COMPARTMENTS AND |
| TOILET ROOMS. FAC SECS.604.3 & 606.2. |
| 7) VERTICAL ACCESSIBILITY IS REQUIRED TO THE SECOND |
| FLOOR PER THE 2010 FAC SEC.201.1.1. |
| 8) FLOOR DRAINS AND HOSE BIBBS ARE REQUIRED IN THE |
| GROUP TOILET ROOMS PER THE 2010 FBC SEC.443.3.5.6. |
| 9) SHT. P4.1 - CLINIC RESTROOM - THERE IS AN ARROW THAT |
| POINTS TO "2 " SANITARY UP" BUT NOTHING IS SHOWN. |
| CLRIFY. |
| 10) SHT.P4.1 - ADULT RESTROOM # 1-103 - THE LAYOUT ON |
| THE RISER DOESN'T CORRELATE WITH THE FLOOR PLAN. |
| CLARIFY. |
| 11) SHT. P4.1 - THE 2" LINE ON RISER BY EWC SAYS 2" |
| SANITARY UP BUT IS NOT CONNECTED TO THE BUILDING DRAIN |
| & TERMINATES NOWHERE. CLARIFY. |
| 12) SHT. P4.1 - A WATER CLOSET IS MISSING FROM THE |
| RISER FOR TOILET ROOMS 1-106 & 1-107A. |
| 13) THE SANITARY RISER APPEARS TO MISSING PIPING FROM |
| RESTROOMS 106-A & 107-A. |
| 14) SHT. P4.1 - SINK SK-1 IN THE ART LAB IS NOT |
| CONNECTED TO THE SANITARY SYSTEM. |
| 15) SUBMIT SPECIFICATIONS ON THE SOLIDS INTERCEPTOR |
| ZURN ZA - 1184. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 16) SHT. P4.1 - SIZE THE VENT FOR SINK SK-1 IN THE ART |
| LAB. |
| 17) SHT.P4.1 - THE ARE NUMEROUS SECTIONS OF THE |
| SANITARY RISER WHERE PIPNG HAS NO CONNECTION POINTS AND |
| TERMINATES NOWHERE. SUBMIT A SANITARY RISER DIAGRAM |
| THAT CLEARLY REFLECTS ALL AREAS OF THE INSTALLATION. |
| EXPAND THE CONDENSED AREAS OF THE RISER DIAGRAM SO IT |
| IS CLEAR AND LEGIBLE. WPB AMEND. TO 2010 FBC SEC. |
| 107.3.5.1.3. |
| 18) SHT. P4.1 - PLUMBING FIXTURE SCHEDULE - THE MINIMUM |
| TRAP SIZE FOR SINKS SHALL BE 1 1/2" NOT 1 1/4" AS SHOWN |
| PER FPC TABLE 709.1. |
| 19) SHT. P4.2 - SIZE ALL SECTIONS OF THE WATER RISER. |
| WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| 20) SHT. P4.2 HAS NOTATION "WC-1" BUT NOTHING IS SHOWN. |
| REFER TO SHT. P3.1 FOR LOCATION. SEE AREA BY GRID LINE |
| H11. |
| 21) SIZE THE WATER RISERS TO THE 2ND FLOOR. |
| 22) SHT. P5.3 - A COMPLETE AND THOROUGH REVIEW CANNOT |
| BE ACCOMPLISHED ON THE STORMWATER RISER BECAUSE IT IS |
| INCOMPLETE; LINES TERMINATE NOWHERE, LINES ARE MISSING, |
| ETC. SUBMIT A COMPLETE, CLEAR AND LEGIBLE STORMWATER |
| RISER DIAGRAM FOR REVIEW. WPB AMEND. TO 2010 FBC SEC. |
| 107.3.5.1.3. |
| 23) SHT. P5.2 - THE DESIGN OF THE STORMWATER SYSTEM |
| SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT |
| DIVERTS WATER TO THE ROOF. SHOW THAT THE AREA OF THE |
| PARAPET WALL HAS BEEN ADDED INTO THE STORMWATER DESIGN |
| PER THE 2010 FPC SEC.1106.4. |
| 24) SHT. P7.1 - THE PLAN SHOWS THE WATER HEATER BEING |
| BOTTOM FED BY THE RECIRCULATING LINE. A VACUUM RELIEF |
| VALVE IS REQUIRED ON THIS LINE PER SEC. 504.2 OF 2010 |
| FPC. |
| 25) SHT. P7.2 - THE DOMESTIC WATER DEMAND TABLE REFERS |
| TO TABLE E103.2(2). THERE IS NO SUCH TABLE . CLARIFY. |
| 26.) DOES THIS SCHOOL ALSO HAVE DAYCARE OR WILL IT BE |
| USED AS A DAYCARE FACILITY AT ANY TIME? DAYCARE |
| FACILITIES SHALL COMPLY W/ 2010 FBC SEC. 436. |
| |
| |