Plan Review Notes
Plan Review Notes For Permit 15020937
Permit Number 15020937
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-21 10:25:45PLAN DENIED
 1) REFER TO SECTION 1022.4 PENETRATIONS 2010 FBC
 ( MINI SPLITS IN STAIRWELL )
 2) PROVIDE A DETAIL SHOWING THE CONDENSER STAND
 TIEDOWN TO ROOF AND CONDENSER TIE DOWN TO STAND
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
  