Plan Review Notes
Plan Review Notes For Permit 15020937
Permit Number 15020937
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-03-06 16:55:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 1.1 DOOR 1-004; DOOR 1-191; SHEET LS 1.2
 DOOR1-209; EXIT DOOR LEAF ENCROACHMENT.
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A
 LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT MORE
 THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
 2) SHEET LS 1.1 THE WALLS OF ROOMS 1-112, 1-190 AND
 1-290 ARE REQUIRED TO BE 1 HOUR FIRE RATED.
  
 3) SHEET LS1.1 & 1.2 STAIRWELL 1-003 ENCLOSURE AND
 PROTECTION OF STAIRS. THE UNPROTECTED WINDOW OPENINGS
 OF THIS STAIRWELL AND/OR ASSOCIATED EXTERIOR WALLS
 WITHIN 10 FT SHALL BE PROTECTED WITH AN 1 HOUR FIRE
 RATING.
 7.2.2.5.2 EXPOSURES.
 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED
 OPENEINGS ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER
 THAN AN EXISTING STAIRWAY, AND THE WALLS OR OPENINGS
 ARE EXPOSED BY
 OTHER PARTS OF THE BUILDING AS AN ANGLE OF LESS THAN
 180 DEGREES, THE BUILDING ENCLOSURE WALLS WITHIN 10 FT
 HORIZONTALLY OF THE NONRATED WALL OR UNPROTECTED
 OPENING SHALL BE
 CONSTRUCTED AS REQUIRED FOR STAIRWAY ENCLUSRES,
 INCLUDING OPENING PROTECTIVES.
  
 4) A DOOR SCHEDULE INDICATING ALL DOOR FIRE RATINGS,
 HARDWARE, FINISH, AND/OR LOCKING DEVICES IS NOT
 ATTACHED TO THIS SUBMITTED PLAN OR IS NOT READILY
 IDENTIFIABLE. THE FIRE RATING OF DOORS CAN NOT BE
 REVIEWED, CONFIRMED OR APPROVED.
  
 5) THE CURVED STAIR SHALL BE PROTECTED WITH THE
 REQUIREMENTS OF NFPA 101 8.6 AND NFPA 13, 8.15 SPECIAL
 SITUATIONS INCLUDING, BUT NOT LIMITED TO, SPRINKLER
 PROTECTION UNDER THE STAIRS.
  
 6) SHEET FS 2.1 & 2.2 , FIRE SPRINKLER PROTECTION WAS
 NOT INDICATED IN THE COMMON HALLWAYS, WITHIN THE
 STAIRWELLS AND THE OPEN ATIURM. A COMPLETE FIRE
 SPRINKLER IS REQUIRED IN THIS OCCUPANCY.
  
 7) AN EXIT SIGN IS REQUIRED AT THE BOTTOM OF THE CURVED
 STAIR AT DOOR 1-005 LEADING TO THE EXIT CORRIDOR.
  
 8) SOME OF THE CURRENT FIRE CODE LISTINGS INDICATED
 WITHIN THE SUBMITTED PLAN ARE INCORRECT AND NEED TO BE
 UPDATED WHERE APPLICABLE. THE PROPOSED PROJECT SHALL
 MEET THE REQUIREMENTS OF THE 5TH EDITION OF FLORIDA
 FIRE PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA
 1 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 9) ADDITIONAL COMMENTS MAY BE APPLIED IN THE FUTURE
 BASED ON THE RESUBMITTAL OF THE ABOVE.
  
  