Plan Review Notes For Permit 15020937 |
Permit Number |
15020937 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-04-14 12:47:31 | 15020937 | | 1901 S. FLAGLER DRIVE | | NEW BUILDING FOR PALM BEACH DAY ACADEMY | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | SHEET E4.2 | | ORANGE COLOR CODING OF CONDUCTORS IS RESERVED FOR HIGH | | LEG DELTASYSTEMS ONLY. NEC 110.15 | | | | SHEET E4.2 | | ON THE ELECTRICAL PLAN PROVIDE A SAFETY LABELING | | SCHEDULE FOR FLASH PROTECTION FOR THE SERVICE, PANEL | | BOARDS AND MAIN DISCONNECTING MEANS. NEC 110.22 | | | | INDICATE THE LOCATION OF THE UTILITY TRANSFORMER AND | | ELECTRICAL SERVICE CONDUCTORS ON THE ELECTRICAL SITE | | PLAN. NEC 215.5 | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | SYSTEMS, SECURITY, SITE LIGHTING AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | [email protected] | | | | |
|