Plan Review Notes
Plan Review Notes For Permit 15020886
Permit Number 15020886
Review Stop E
Sequence Number 1
Notes
Date Text
2015-03-03 10:42:33PROVIDE MANUFACTURER PRODUCT APPROVALS ON SITE FOR THE
 INSPECTOR. NEC 110.3(B)
 VERIFY NEW LOAD DOES NOT EXCEED CAPACITY OF EXISTING
 ELECTRICAL PANEL AND/OR SERVICE.
 VERIFY NEW EQUIPMENT VOLTAGE IS CONSISTANT WITH
 EXISTING SYSTEM VOLTAGE.