2015-05-21 08:32:56PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE SIZE OF THE RETURN AIR "JUMPER" (DUCT
 AND GRILL) BETWEEN THE HALL AND THE GUEST ROOM. SPECIFY
 WHAT TYPE OF "JUMPER" (A TRANSFER DUCT OR A TRANSFER
 GRILL) WILL BE USED. FBC-R M1602.4
  
 2) ONLY THE SUMMARY PAGE FOR THE EQUIPMENT SIZING
 CALCULATIONS WAS SUBMITTED. SUBMIT THE COMPLETE
 CALCULATIONS. FBC 107.2.1 & ENERGY CODE SECTION 403.6.1
  
 3) SPECIFY ON THE PLAN THAT THERE IS A LOUVERED DOOR ON
 THE AIR HANDLER CLOSET FOR RETURN AIR. FBC-R M1602.4
  
 4) THE SQUARE FOOTAGE OF THE GUEST HOUSE CONVERSION IS
 500 SQFT ON THE MECHANICAL PLANS AND 529 SQFT ON THE
 ARCHITECTURAL PLANS. FBC 107.2.1
  
 5) FORM 402 IS NOT CORRECT AND INCOMPLETE. BASED ON THE
 INFORMATION ON THE FORM, THE PROJECT WILL NOT COMPLY
 USING THIS METHOD. THE PERFORMANCE METHOD, SECTION 405
 OF THE ENERGY CODE CAN BE USED TO SHOW COMPLIANCE.
  
  