Plan Review Notes For Permit 15020865 |
Permit Number |
15020865 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2015-05-21 08:32:56 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE SIZE OF THE RETURN AIR "JUMPER" (DUCT | | AND GRILL) BETWEEN THE HALL AND THE GUEST ROOM. SPECIFY | | WHAT TYPE OF "JUMPER" (A TRANSFER DUCT OR A TRANSFER | | GRILL) WILL BE USED. FBC-R M1602.4 | | | | 2) ONLY THE SUMMARY PAGE FOR THE EQUIPMENT SIZING | | CALCULATIONS WAS SUBMITTED. SUBMIT THE COMPLETE | | CALCULATIONS. FBC 107.2.1 & ENERGY CODE SECTION 403.6.1 | | | | 3) SPECIFY ON THE PLAN THAT THERE IS A LOUVERED DOOR ON | | THE AIR HANDLER CLOSET FOR RETURN AIR. FBC-R M1602.4 | | | | 4) THE SQUARE FOOTAGE OF THE GUEST HOUSE CONVERSION IS | | 500 SQFT ON THE MECHANICAL PLANS AND 529 SQFT ON THE | | ARCHITECTURAL PLANS. FBC 107.2.1 | | | | 5) FORM 402 IS NOT CORRECT AND INCOMPLETE. BASED ON THE | | INFORMATION ON THE FORM, THE PROJECT WILL NOT COMPLY | | USING THIS METHOD. THE PERFORMANCE METHOD, SECTION 405 | | OF THE ENERGY CODE CAN BE USED TO SHOW COMPLIANCE. | | | | |
|