Plan Review Notes For Permit 15020865 |
Permit Number |
15020865 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-04-20 18:05:56 | PLAN REVIEW COMMENTS | | | | 3RD REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW | | SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R | | M15. | | | | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | 3) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN | | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT | | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. | | | | 4) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION | | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER | | CONSTRUCTION DOCUMENTS FOR THE ADDITION AND CONVERTED | | GARAGE. | | | | |
|