2015-03-12 10:26:40 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. PLANS TO BE ARCHITECTURAL QUALITY, TO SCALE. TEXT ON |
| THE PLAN IS IN THREE DIFFERENT ORIENTATIONS. PLANS |
| SHOULD BE READABLE WITHOUT ROTATION. APPLICATION IS FOR |
| "FLOORS, DOORS, KITCHEN, PAINT." PLANS SHOULD REFLECT |
| WORK PROPOSED, FBC 107. |
| |
| 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER |
| SHEET, FAC9N-3. THIS SHOWS THE NUMBER AND STATUS. ON |
| THE EVALUATION REPORT PROVIDED, INDICATE WHICH OF THE |
| DOORS IS PROPOSED. |
| |
| 3. FOR THE TWO STORY BUILDING, LABEL THE UNITS. IF THE |
| FLOOR CEILING ASSEMBLY IS A TENANT SEPARATION, PROVIDE |
| FLOORING UNDERLAYMENT TEST REPORTS: |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| NOT BE ALTERED. |
| |
| PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| BELOW WILL NOT BE ALTERED. |
| |
| PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| |
| IF THE FLOOR/CEILING ASSEMBLY IS NOT A TENANT |
| SEPARATION, FLOORING UNDERLAYMENT INFORMATION NOT |
| REQUIRED. |
| |
| 4. KITCHEN RENOVATION IS PROPOSED. PLANS SHOULD SHOW |
| EXISTING AND PROPOSED. INCLUDE ANY PLUMBING AND |
| ELECTRICAL WORK. |