Plan Review Notes
Plan Review Notes For Permit 15020859
Permit Number 15020859
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-12 10:26:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS TO BE ARCHITECTURAL QUALITY, TO SCALE. TEXT ON
 THE PLAN IS IN THREE DIFFERENT ORIENTATIONS. PLANS
 SHOULD BE READABLE WITHOUT ROTATION. APPLICATION IS FOR
 "FLOORS, DOORS, KITCHEN, PAINT." PLANS SHOULD REFLECT
 WORK PROPOSED, FBC 107.
  
 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEET, FAC9N-3. THIS SHOWS THE NUMBER AND STATUS. ON
 THE EVALUATION REPORT PROVIDED, INDICATE WHICH OF THE
 DOORS IS PROPOSED.
  
 3. FOR THE TWO STORY BUILDING, LABEL THE UNITS. IF THE
 FLOOR CEILING ASSEMBLY IS A TENANT SEPARATION, PROVIDE
 FLOORING UNDERLAYMENT TEST REPORTS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 IF THE FLOOR/CEILING ASSEMBLY IS NOT A TENANT
 SEPARATION, FLOORING UNDERLAYMENT INFORMATION NOT
 REQUIRED.
  
 4. KITCHEN RENOVATION IS PROPOSED. PLANS SHOULD SHOW
 EXISTING AND PROPOSED. INCLUDE ANY PLUMBING AND
 ELECTRICAL WORK.