2015-09-01 07:59:032ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15020858
 9/1/12015
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW ON
 3/21/15, PROVIDE FRESH AIR CALCULATIONS ON THE PLAN IN
 COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL. INDICATE
 ON THE PLAN THE REQUIRED AMOUNT OF VENTILATION AIR IN
 CFM'S, AND THE AMOUNT BEING PROVIDED BY THE EXISTING
 SYSTEM- SEE SECTION 909.1 FBC-10 EXISTING BUILDING
 CODE.
 2) PLEASE SHOW THE LAYOUT OF THE EXISTING AC SYSTEM ON
 THE PLAN AND PROVIDE DETAILS- LOCATIONS OF THE AIR
 HANDLER AND CONDENSER, COOLING AND HEATING CAPACITIES
 OF THE SYSTEM, SUPPLY AND RETURN AIR DUCT RUNS, AND
 LOCATIONS OF DUCT SMOKE DETECTORS AND FIRE DAMPERS IF
 APPLICABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  