Plan Review Notes For Permit 15020858 |
Permit Number |
15020858 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-09-01 07:59:03 | 2ND REVIEW: FBC 2010 MECHANICAL | | PERMIT #15020858 | | 9/1/12015 | | | | 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW ON | | 3/21/15, PROVIDE FRESH AIR CALCULATIONS ON THE PLAN IN | | COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL. INDICATE | | ON THE PLAN THE REQUIRED AMOUNT OF VENTILATION AIR IN | | CFM'S, AND THE AMOUNT BEING PROVIDED BY THE EXISTING | | SYSTEM- SEE SECTION 909.1 FBC-10 EXISTING BUILDING | | CODE. | | 2) PLEASE SHOW THE LAYOUT OF THE EXISTING AC SYSTEM ON | | THE PLAN AND PROVIDE DETAILS- LOCATIONS OF THE AIR | | HANDLER AND CONDENSER, COOLING AND HEATING CAPACITIES | | OF THE SYSTEM, SUPPLY AND RETURN AIR DUCT RUNS, AND | | LOCATIONS OF DUCT SMOKE DETECTORS AND FIRE DAMPERS IF | | APPLICABLE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|