Plan Review Notes
Plan Review Notes For Permit 15020858
Permit Number 15020858
Review Stop E
Sequence Number 2
Notes
Date Text
2015-10-05 19:55:45PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 THE PREVIOUSLY REQUIRED ITEMS AS REQUESTED FROM THE
 PREVIOUS ELECTRICAL PLANS REVIEW BACK IN FEBRUARY OF
 THIS YEAR HAVE NOT BEEN ADDRESSED AND A RESPONSE OF NO
 MEANING HAS BEEN SUBMITTED INSTEAD.
 FOR A SUCCESSFUL ELECTRICAL PLANS REVIEW YOU SHALL
 SUBMIT THE FOLLOWING:
 1. YOU SHALL INDICATE ON AN ELECTRICAL FLOOR PLAN THE
 LOCATION OF ALL OVER CURRENT PROTECTION DEVICES
 (PANELS) AS WELL AS ALL THE MAIN BREAKERS IF LOCATED
 ELSEWHERE.
 2. YOU SHALL PROVIDE A SITE SPECIFIC ELECTRICAL LOAD
 CALC.
 3. YOU SHALL SUBMIT A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM INCLUDING WIRING SIZING.
 4. YOU SHALL PROVIDE A PANEL SCHEDULE/CIRCUIT DIRECTORY
 AS REQUIRED BY NEC
 5. YOU SHALL INCLUDE ON THE ELECTRICAL FLOOR PLAN THE
 LOCATION OF ALL EMERGENCY AND EXIT LIGHTS.
 REGARDLESS OF WHAT YOUR ARCHITECT CLAIMS, FOR REASONS
 OF LIFE SAFETY THERE ARE DIFFERENT ELECTRICAL AND FIRE
 ALARM REQUIREMENTS FROM ASSEMBLY OCCUPANCY TO REGULAR
 BUSINESS OCCUPANCY. THEREFORE THERE MAY BE WIRING
 METHODS WITHIN THE PREMISES THAT THOUGH PERMITTED IN A
 BUSINESS ENVIRONMENT, WILL BE AGAINST CODE IN AN
 ASSEMBLY ENVIRONMENT. THE SAME HOLDS TRUE FOR THE FIRE
 ALARM AND EMERGENCY LIGHTING REQUIREMENTS.
 FURTHERMORE, LET ME CLARIFY THAT THIS WAS NEVER PASSED
 OR APPROVED BY THE FIRE PLANS EXAMINER, IF YOU READ HIS
 NOTES, HE INSTRUCTED YOU TO SUBMIT A SEPARATE FIRE
 ALARM DRAWING FOR APPROVAL AS THE FIRE ALARM HAS TO BE
 ON A STAND-ALONE PERMIT WITH ITS OWN SUBMITTAL
 DOCUMENTS.
 PLEASE REVISE YOUR PLANS ACCORDING FOR A SMOOTH AND
 SUCCESSFUL REVIEW.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DO NOT HESITATE
 TO CONTACT ME.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  