Plan Review Notes For Permit 15020858 |
Permit Number |
15020858 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-17 08:52:13 | 1) THIS FACILITY IS DEEMED A CHANGE OF OCCUPANCY FROM | | BUSINESS TO A-3. THE NEW OCCUPANCY SHALL COMPLY WITH | | SECTION 910.1 OF THE 2010 FL. EXISTING BUILDING CODE | | AND TABLE 403.1 OF THE 2010 FL. PLUMBING CODE. SEPARATE | | SANITARY FACILITIES ARE REQUIRED FOR THA MALES AND | | FEMALES PER THE 2010 FPC SEC.403.1. A MINIMUM OF ONE | | WATER CLOSET AND ONE LAVATORY IS REQUIRED FOR EACH SEX | | PER TABLE 403.1 OF THE 2010 FL. PLUMBING CODE. | | 2) A SERVICE SINK IS REQUIRED IN THE FACILITY PER ABLE | | 403.1 OF THE 2010 FL. PLUMBING CODE. | | 3) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER | | THE 2010 FL. ACCESSIBILITY CODE SEC. 211.2. ONE | | FOUNTAIN SHALL COMPLY WITH FAC SEC.602.1 THROUGH | | SEC.602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | SEC. 602.7. SEE EXCEPTION FOR SINGLE DRINKING | | FOUNTAIN.SHOW THE LOCATION OF THE DRINKING FOUNTAINS ON | | THE FLOOR PLAN. | | 4) THE DRINKING FOUNTAINS SHALL BE PROVIDED WITH CLEAR | | FLOOR SPACE AND KNEE AND TOE CLEARANCE PER THE 2010 FL. | | ACCESSIBILITY CODE SECS. 305 & 306. SHOW THE REQUIRED | | CLEAR FLOOR SPACE ON THE PLAN. | | 5) THE TOILET ROOMS SHALL COMPLY WITH SEC. 213.2 AND | | SEC. 603 OF THE 2010 FAC. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|