 PROJECT: CHANGE OF OCCUPANCY; BRIDGE CHURCH SCHOOL
 PERMIT#: 15020858
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 ELECTRICAL PLANS HAVE NOT BEEN PROVIDED WITH THIS
 SUBMITTAL BUT THE MINIMUM CONDITIONS OF THE NEC MUST BE
 MET AND INDICATED ON THE PLANS SUBMITTED FOR CODE
 COMPLIANCE. PLEASE INDICATE COMPLIANCE WITH THE
 FOLLOWING:
  
 1) NEC 240.24 (B) OCCUPANCY.
 EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL
 OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING
 THAT OCCUPANCY. INDICATE ON THE PLANS THE LOCATIONS OF
 ALL ELECTRICAL PANEL
  
 2) NEC 518 ASSEMBLY OCCUPANCY.
 WIRING METHODS AND ELECTRICAL SYSTEMS SHALL BE
 INSTALLED IN COMPLIANCE WITH THE MINIMUM CONDITIONS
 FOUND IN THE NEC ARTICLE 518.
  
 3) NEC 422.52 ELECTRIC DRINKING FOUNTAINS.
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  