| PROJECT: CHANGE OF OCCUPANCY; BRIDGE CHURCH SCHOOL |
| PERMIT#: 15020858 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| ELECTRICAL PLANS HAVE NOT BEEN PROVIDED WITH THIS |
| SUBMITTAL BUT THE MINIMUM CONDITIONS OF THE NEC MUST BE |
| MET AND INDICATED ON THE PLANS SUBMITTED FOR CODE |
| COMPLIANCE. PLEASE INDICATE COMPLIANCE WITH THE |
| FOLLOWING: |
| |
| 1) NEC 240.24 (B) OCCUPANCY. |
| EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL |
| OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING |
| THAT OCCUPANCY. INDICATE ON THE PLANS THE LOCATIONS OF |
| ALL ELECTRICAL PANEL |
| |
| 2) NEC 518 ASSEMBLY OCCUPANCY. |
| WIRING METHODS AND ELECTRICAL SYSTEMS SHALL BE |
| INSTALLED IN COMPLIANCE WITH THE MINIMUM CONDITIONS |
| FOUND IN THE NEC ARTICLE 518. |
| |
| 3) NEC 422.52 ELECTRIC DRINKING FOUNTAINS. |
| ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH |
| GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |