Plan Review Notes
Plan Review Notes For Permit 15020858
Permit Number 15020858
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-14 09:47:11 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020858
 ADD: 525 PALM ST. SUITE B
 CHANGE OF OCCUPANCY
 CONT: TBD
 TEL: (561)667-3661
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: SAT. MARCH 14/ 2015
 ACTION: DENIED
  
 1) PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY AND WILL
 REQUIRE ADDITIONAL INFORMATION FOR THE COMPLETION OF
 THE CERTIFICATE OF OCCUPANCY.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED. PLEASE REVIEWOCCUPANCY LOAD/EGRESS
 REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 BLDG. IS FIRE SPRINKLERED OR NOT
 LIFE SAFETY SHALL BE DETERMINED AND SHALL INCLUDE THE
 FOLLOWING ININFORMATION:
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS OR NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 SPECIFIC OCCUPANCY REQUIREMENTS :DAYCARE
 CONSTRUCTION REQUIREMENTS MINIMUM BLDG TYPE
  
 2) IN REVIEWING THESE PLANS THE 2010 FBC-B OCCUPANCY
 LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
  
 2) IN REVIEWING THESE PLANS THE OCCUPANCY
 CLASSIFICATION IS DEFINED UNDER SECTION 2010 FBC-B
 303.1 EXCEPTION # 5. ACCESSORY RELIGIOUS EDUCATIONAL
 ROOMS AND RELIGIOUS AUDITORIUMS WITH OCCUPANT LOADS OF
 LESS THAN 100 ARE NOT CONSIDERED SEPARATE OCCUPANCIES.
 THERE FOR THIS OCCUPANCY SHALL BE CLASSIFIED AS A A3
 OCCUPANCY. UNLESS THIS SAME EDUCATIONAL ROOMS WILL BE
 USED AS A DAYCARE FACILITY DURING THE WORK WEEK. PLEASE
 INDICATE AS SUCH, BECAUSE IT WILL THEN FALL UNDER THE
 FBC-B CHAPTER 436 DAY-CARE OCCUPANCIES. NOTE IF THIS
 AREA IS DAYCARE IT WILL BE CONSIDERED A MIXED USE
 OCCUPANCY BETWEEN DAYCARE AND EDUCATIONAL, THE MOST
 STRINGENT REQUIEMENTS OF EITHER OCCUPANCY WILL BE THE
 CODE SECTION REQUIRED TO ACHIEVE.
  
 3) IT IS ASSUMED THIS BUILDING IS NOT FIRE SPRINKLERED,
 IN DOING SUCH WITH THE A3 OCCUPANCY 930 SQ FT/ 15= 62
 OCCUPANTS AND WILL REQUIRE 2 EXITS 1/2 THE DIAGONAL
 DISTANCE OF THE ROOM APART. THE 1/2 THE DIAGONAL
 DISTANCE IS APPROXIMATELY 26 FT APART AND THE DOORS ARE
 ONLY 18 FT APART. PLEASE SEE THE 2010 FBC-B TABLE
 1015.1 WILL REQUIRED 2 EXITS SINCE THE OCCUPANT LOAD IS
 GREATER THAN 49 OCCUPANTS.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER