Plan Review Notes
Plan Review Notes For Permit 15020847
Permit Number 15020847
Review Stop E
Sequence Number 2
Notes
Date Text
2015-03-13 10:26:223/13/2015
 PROJECT: SITE LIGHTING
 PERMIT#: 15020847
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. A TIME SWITCH IS NOTED ON
 SHEET E101 HOWEVER THERE IS NO NOTES OR PRODUCT
 APPROVAL ON TIME SWITCH THAT INDICATE COMPLIANCE WITH
 FBC 505.2. PROVIDE PRODUCT APPROVAL ON TIME SWITCH.
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL LIGHT
 POLE CONFIGURATIONSINCLUDING LUMINAIRE IN COMPLIANCE
 WITH THE FBC 1609.
  
 3) NEC 215.5
 PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL PANELS
 AND SERVICE PROPOSED TO FEED THE LIGHT POLES.
  
 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]