2015-03-17 13:06:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | A LIFE SAFETY PLAN WAS NOT SUBMITTED AND IS REQUIRED TO | | INCLUDE, PATH OF TRAVEL, EXIT SIGNAGE, LIGHTING, ETC | | | | THE CONSTRUCTION/INSTALLATION OF THE LADDERS AND BRIDGE | | SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 101, CHAPTER | | 7, 7.2.9. | | | | THERE IS NO INDICATION OF A STEP-DOWN (OR STEP-UP) | | DIMENSION AT THE BRIDGE CONNECTING TO THE BUILDING. | | BASED ON THE HEIGHT OF THE STEPS ADDITIONAL STEPS MAY | | BE NEEDED. | | | | THE ENDS OF THE HAND RAIL ON THE BRIDGE SHALL EXTEND | | PASSED THE END OF THE WALKWAY CONSISTANT WITH THE | | REQUIREMENTS OF 7.2.2.4 FOR ANY STEP DOWN (UP) OR | | APPROACH TO THE EDGE OF THE BUILDING. | | | | THERE IS NO DIMENSION INDICATED OF THE HEIGHT OF THE | | LAST LADDER RUNG TO THE GROUND. | | | | | | | | |
|