Plan Review Notes
Plan Review Notes For Permit 15020744
Permit Number 15020744
Review Stop E
Sequence Number 3
Notes
Date Text
2015-06-24 14:48:446/9/2015
 PROJECT: RESIDENTIAL RENNOVATION
 PERMIT#:15020744
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) DISCONNECT REQUIRED FOR WATER HEATER. NEC 422.31
  
 2) BUILDINGS OR STRUCTURES SUPPLIED BY FEEDERS SHALL
 HAVE A GROUNDING ELECTRODE OR GROUNDING ELECTRODE
 SYSTEM INSTALLED IN ACCORDANCE WITH PART III OF ARTICLE
 250. THE GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE
 CONNECTED IN ACCORDANCE WITH 250.32(B) OR (C). NEC
 250.32(A)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  