Plan Review Notes For Permit 15020744 |
Permit Number |
15020744 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-06-24 14:48:44 | 6/9/2015 | | PROJECT: RESIDENTIAL RENNOVATION | | PERMIT#:15020744 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN | | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) DISCONNECT REQUIRED FOR WATER HEATER. NEC 422.31 | | | | 2) BUILDINGS OR STRUCTURES SUPPLIED BY FEEDERS SHALL | | HAVE A GROUNDING ELECTRODE OR GROUNDING ELECTRODE | | SYSTEM INSTALLED IN ACCORDANCE WITH PART III OF ARTICLE | | 250. THE GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE | | CONNECTED IN ACCORDANCE WITH 250.32(B) OR (C). NEC | | 250.32(A) | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|