2015-06-09 11:25:036/9/2015
 PROJECT: RESIDENTIAL RENNOVATION
 PERMIT#:15020744
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE RISER DIGRAM INDICATES A # 6 FEEDER TO THE
 100AMP SUB PANEL IN THE GUEST HOUSE. $6 CU IS NOT
 APPROVED FOR THE TOTAL CONNECTED DEMAND LOADS OF 85
 AMPS OR THE 100AMP OCPD .
  
 2) OUTLETS IN THE KITCHEN SHALL MEET THE PROVISIONS OF
 THE NEC 210.52(A)(2)
  
 3) OUTLETS IN THE BALANCE OF THE DWELLING SHALL MEET
 THE PROVISIONS OF THE NEC 210.52(A)(1)
  
 4) SMOKE DETECTORS ARE REQUIRED TO MEET THE
 REQUIREMENTS OF THE FBC FOR THE INSTALLATION OF SMOKE
 DETECTORS. FBC R 314.3.1
 FBC R 314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 5) PROVIDE AND INDICATE THE PROVISIONS FOR A NEW
 CIRCUIT FOR THE MINI SPLIT SYSTEM INDICATED ON THE 1ST
 FLOOR PLAN ON SHEET 1. THE CIRCUIT SHALL BE INDICATED
 IN THE PANEL SCHEDULE AND THE LOAD CALCULATION
 INDICATING THE AVIALABLE CURRENT FOR THE ADDITION OF
 THE NEW CIRCUIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  