2015-06-09 11:25:03 | 6/9/2015 |
| PROJECT: RESIDENTIAL RENNOVATION |
| PERMIT#:15020744 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) THE RISER DIGRAM INDICATES A # 6 FEEDER TO THE |
| 100AMP SUB PANEL IN THE GUEST HOUSE. $6 CU IS NOT |
| APPROVED FOR THE TOTAL CONNECTED DEMAND LOADS OF 85 |
| AMPS OR THE 100AMP OCPD . |
| |
| 2) OUTLETS IN THE KITCHEN SHALL MEET THE PROVISIONS OF |
| THE NEC 210.52(A)(2) |
| |
| 3) OUTLETS IN THE BALANCE OF THE DWELLING SHALL MEET |
| THE PROVISIONS OF THE NEC 210.52(A)(1) |
| |
| 4) SMOKE DETECTORS ARE REQUIRED TO MEET THE |
| REQUIREMENTS OF THE FBC FOR THE INSTALLATION OF SMOKE |
| DETECTORS. FBC R 314.3.1 |
| FBC R 314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| 5) PROVIDE AND INDICATE THE PROVISIONS FOR A NEW |
| CIRCUIT FOR THE MINI SPLIT SYSTEM INDICATED ON THE 1ST |
| FLOOR PLAN ON SHEET 1. THE CIRCUIT SHALL BE INDICATED |
| IN THE PANEL SCHEDULE AND THE LOAD CALCULATION |
| INDICATING THE AVIALABLE CURRENT FOR THE ADDITION OF |
| THE NEW CIRCUIT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |