2015-06-20 12:06:31 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED |
| PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). |
| |
| 1) ELECTRICAL PERMIT REQUIRED. |
| |
| 2) THE SITE PLAN IS NOT SIIGNED OR SEALED. ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. FBC, WPB AMENDMENTS 107.2.1 |
| 1A) 471.025 668.001-668.006. |
| ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR |
| DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING |
| FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS |
| PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE |
| SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH |
| SAID SEAL. |
| |
| 3) THE LOAD FROM THE ENGINEER INDICATES A 95.75 AMP |
| LOAD ON A 100AMP SERVICE. THE ELECTRICAL CONTRACTOR |
| ALSO SUBMITTED A LOAD CALCULATION INDICATING A 54.27AMP |
| LOAD ON THE TRAILER AND ANOTHER 46.15AMP LOAD FOR THE |
| JOBSITE TEMPORARY POWER PANEL. CLARIFICATION IS |
| REQUIRED. PROVIDE A REVISED LOAD CALCULATION TO THE |
| ELECTRICAL INSPECTOR IN THE FIELD SIGNED BY THE |
| ENGINEER OF RECORD REVISING THE LOAD CALCULATION |
| SUBMITTED PREVIOUSLY ON PG 2 OF 4. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |