 1) PROVIDE A LOAD CALCULATION TO INDICATE TOTAL
 CONNECTED LOAD FOR THE SIZE OF THE MAIN SERVICE OCPD.
 AND THE OCPD FEEDING THE TRAILER.
 2) INDICATE THE LOCATION ON THE SITE FOR THE ELECTRICAL
 SERVICE EQUIPMENT IN RELATION TO THE CONSTRUCTION
 TRAILER. THE SITE PLAN INDICATES THE LOCATION OF AN
 "EXISTING TRANSFORMER". IS THIS A UTILITY TRANSFORMER
 WITH ADAQUATE CAPACITY?
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471,
 668.001-668.006
 FBC, WPB AMENDMENTS 107.2.1. THE SITE PLAN AND
 ELECTRICAL RISER DIAGRAM HAVE NOT BEEN SIGNED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]