Notes |
Date |
Text |
2015-03-07 04:52:46 | 1) SUBMIT A SITE PLAN SHOWING THE CONNECTION AND | | LOCATION OF THE WATER & SEWER SYSTEM TO THE MODULAR | | BUILDING. THE MINIMUM SIZE WATER SERVICE TO THE | | STRUCTURE SHALL BE 3/4" PER 2010 FPC SEC.603.1. | | 2) AN APPROVED BACKFLOW PREVENTER SHALL BE INSTALLED ON | | THE WATER SERVICE AT THE METER PER WPB CITY ORDINANCE | | SEC.90-33. A MINIMUM OF A REDUCED PRESSURE ZONE | | BACKFLOW PREVENTION ASSEMBLY PER THE CITY OF WPB CROSS | | CONNECTION MANUAL & 2010 FPC SEC.608.1.SUBMIT 2 COPIES | | OF THE MANUF. SPECIFICATIONS FOR THE BFP DEVICE. | | 3) INDICATE ON THE PLAN IF THE BUILDING WILL BE | | CONNECTED TO A SANITARY SEWER OR A HOLDING TANK. IF TO | | A HOLDING TANK, SHOW THE SIZE AND LOCATION OF THE TANK. | | A PERMIT MAY BE REQUIRED FROM THE PALM BEACH COUNTY | | HEALTH DEPT.ALSO, IF TO A HOLDING TANK, SUBMIT A COPY | | OF THE PUMP OUT CONTRACT TO CONFIRM THE TSNK WILL BE | | MAINTAINED IN A SANITARY CONDITION. 2010 FPC SEC.311.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|