Plan Review Notes For Permit 15020685 |
Permit Number |
15020685 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-16 16:56:14 | PROVIDE AN ELECTRICAL SERVICE RISER DIAGRAM TO INDICATE | | THE SERVICE MAIN OCPD CONDUIT AND WIRE SIZES BETWEEN | | THE SERVICE ENTRANCE AND THE FEEDER FROM THE NEW | | TEMPORARY ELECTRICAL SERVICE TO THE CONSTRCTION | | TRAILER. | | PROVIDE A TOTAL CONNECTED LOAD FROM THE MANUFACTURER | | PRODUCT APPROVALS INDICATING THE REQUIRED SIZE OF THE | | MAIN SERVICE OCPD. | | INDICATE THE OCATION ON THE SITE FOR THE ELECTRICAL | | SERVICE EQUIPMENT IN RELATION TO THE CONSTRUCTION | | TRAILER. | | INDICATE APPROVED WIREIN METHODS AND MATERIALS FOR ALL | | OF THE ABOVE. |
|