Plan Review Notes
Plan Review Notes For Permit 15020671
Permit Number 15020671
Review Stop P
Sequence Number 2
Notes
Date Text
2015-03-21 06:19:451) INDICATE ON THE PLAN THE TYPE OF PIPE BEING
 INSTALLED FOR THE GAS SYSTEM. THE RESPONSE FROM THE
 ENGINEER REFERS TO PLUMBING SHT. P0.2 BUT THERE IS NO
 SUCH DRAWING IN THE SET OF SUBMITTED PLANS. CLARIFY.
 2) INDICATE THE DELIVERY PRESSURE OF THE GAS PER THE
 2010 FBC FUEL GAS CODE SEC.402.2. THE RESPONSE FROM THE
 ENGINEER REFERS TO PLUMBING SHT. P0.2 BUT THERE IS NO
 SUCH DRAWING IN THE SET OF SUBMITTED PLANS. CLARIFY.
 3) SUBMIT REFERENCED DRAWING P0.2 FOR REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  